Cleaning the burner and heat exchanger (continued) – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 70

Advertising
background image

60

Service Manual NeoTherm 80 - NeoTherm 285

Disassembly Procedure:
1. Turn off power to the machine. Use the main discon-

nect switch on the front of the machine, just above

the control panel.

2. Remove the front panel.
3. Shut off the gas at the gas shutoff valve on the right

side of the machine (yellow handle).

4. Unplug the wires running to the gas valve. The

connector is keyed, and can only be plugged in one

way.

5. Disconnect the small vacuum hose running to the

top of the gas valve.

6. Disconnect the wires to the blower. There are two

connectors. The power wires run to the rear con-

nector, and the control wires connect to the front.

7. Loosen the left hose clamp on the black rubber air

inlet hose, then pull the left end of the hose away

from the end of the Venturi.

Fig. C5-2 - Gas shutoff valve (typical)

Cleaning the Burner and Heat Exchanger (continued)

Fig. C5-3 - Wiring connector for gas

valve

Fig. C5-4 - Wiring connections for blower

Control

Power

Fig. C5-5 - Loosen the left end of the rubber hose

Hose

C5

cont.

Advertising