Quick Check of Components in the

Safety Interlock Chain - continued

B1

cont.

Fig. B1-8 - Control voltage for the blower

J2

12. If the unit is receiving a “call for heat,” and all of the

safety switches are OK, the blower should be receiv-

ing control voltage through J2 on the control module.

See Fig. B1-8.
If power is available at J2, but the blower is

not running, go to Section B18 - “Checking the

Blower.”

• If the blower is running, and the unit does not

fire, go to Section B28 - “Testing the Temperature

Sensors.”

13. Replace all of the wiring you changed earlier:

• Remove the jumper for the “call for heat” – TB7

5-6)

• Reconnect the outdoor temperature sensor (TB7

1-2)

• Reset the Anti-Short Cycle setting

• If DHW is connected – Remove the DHW jumper

(TB6 5-6)