High Stack Temperature Fault
B20
Yes
No
Correct this immediately.
Blocked exhaust outlet?
Dirty heat exchanger?
If you have the current user interface,
set the stack temperature limit to 190°F.
Actual stack
temperature
problem?
Check the continuity on the wires from
the sensor to J9-4, J9-5, and J9-6 on the
control module.
Wiring to
sensor is correct? Good
connections?
No
Yes
Fault disappears?
No
Replace the control module.
Replace the sensor.
Problem
with circulator
pump?
Yes
No