LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 45

Advertising
background image

35

Service Manual NeoTherm 80 - NeoTherm 285

Procedure - Removing or replacing the switch
1. Turn off power to the machine. Use the main

disconnect switch located above the top of the

control panel.

2. Remove the covers on top of the unit so you can

reach the air pressure switch.

3. Remove the mounting screws on both sides

of the switch. Use the screwdriver or the 5/16”

socket.

4. Use the pliers to release the hose clamps and re-

move the air hoses from the bottom of the switch.

Important! During reassembly, the hoses must

be connected to the correct barbs on the switch.

Do not reverse the connections.

To prevent this, you should mark one of the

hoses. Remove the front hose first. Mark the

rear hose with a piece of electrical tape, then

remove the rear hose.

5. To reassemble, reverse the procedure we have

just described. Be sure to connect the two air

hoses in the correct locations.

Removing and Replacing the Air Pressure Switch (continued)

B17

cont.

Advertising
This manual is related to the following products: