General venting – Vermont Casting DVBR42 User Manual

Page 10

Advertising
background image

10

DVBR Series Direct Vent Gas Fireplace

20000584

2. Carefully remove the square piece of insulation

along the perforations. (Fig. b) Discard insulation.

3. Remove the eight (8) screws securing outer collar

adapter to fireplace. (Be careful not to damage insu-
lation.) (Fig. 10)

4. Set outer collar adapter aside.
5. Remove insulation on top of collector box. (Fig. 11)
6. Remove the four (4) screws securing flue cover to

top of unit and remove flue cover. (Fig. 11)

7. Remove the four (4) screws securing flue pipe to

back of unit. Remove flue pipe. (Fig. 11)

8. Secure flue cover to back of flue outlet. Be sure to

replace gasket. (Fig. 12)

9. Install flue pipe to top of unit with four (4) screws. Be

sure to replace gasket. (Fig. 12)

10. Set insulation in back of unit foil side down.
11. Secure outer collar adapter to unit with the round

collar on top, secure with eight (8) screws.

NOTE: Be sure not to damage any gasket material.

FP1543

remove insulation

1/05

Remove Insulation

FP1543

Fig. b Remove and discard insulation.

Your fireplace is approved to be vented either through
the side wall, or vertical through the roof.
• Only CFM Corporation venting components spe-

cifically approved and labelled for this fireplace
may be used.

• Venting terminals shall not be recessed into a wall or

siding.

• Horizontal venting which incorporates the twist lock

pipe must be installed on a level plane without an
inclining or declining slope.

Horizontal venting which incorporates the use of flex
venting shall have an inclining slope from the unit of
1/2” (13 mm) per12” (305 mm).

There must not be any obstruction such as bushes,
garden sheds, fences, decks or utility buildings within
24” from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent termi-
nation area after snow falls, and clear to prevent ac-
cidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
Location of Vent Termination
It is imperative the vent termination be located observ-
ing the minimum clearances as shown on the following
page.

General Venting