Dvbr series direct vent gas fireplace, Clearance to combustibles, Mantels – Vermont Casting DVBR42 User Manual

Page 6: Mantel chart, Locating your fireplace

Advertising
background image

6

DVBR Series Direct Vent Gas Fireplace

20000584

Clearance to Combustibles

Appliance

Top ......................................................... 0” (0 mm)

Bottom ..................................................... 0” (0 mm)

Side ......................................................... 0” (0 mm)

Back ........................................................ 0” (0 mm)

Perpendicular Sidewall ........................... 0” (0 mm)

Top of unit to ceiling .......................... 36” (914 mm)

Front of unit to combustibles ............. 36” (914 mm)

Venting
Concentric sections of DV Vent ................... 1” (25 mm)
Nonconcentric sections of DV Vent

Sides and bottom ................................. 1” (25 mm)

Top ........................................................ 2” (51 mm)

Mantels

The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths, refer to
Figures 4a and 4b and the Mantel Chart below.
The distances and reference points are not affected by
the fitting of a bay window front trim kit.
Noncombustible mantels and legs may be installed at
any height and width around the appliance. When using
paint or lacquer, it must be heat resistant to prevent
discoloration.

J

F

G

H

I

Mantel

Leg

CFM164a

Mantel Leg Chart

06/22/01 sta

CFM170

DV Builder Front

View

O

N

M

L

K

CFM164a

Side of

Combustion Chamber

CFM170

Mantel Leg

Mantel Leg from Side

Ref.

Depth

Ref. of Combusion Opening

F

14” (356 mm)

K

14”

(356 mm)

G

12” (305 mm)

L

12”

(305 mm)

H

10” (254 mm)

M

10”

(254 mm)

I

8” (203 mm)

N

8”

(203 mm)

J

4” (102 mm)

O

3¹⁄₂” (89 mm)

Fig. 4b Combustible mantel minimum installation.

Black

Surround Face

Mantel Chart

Mantel

Mantel from Top

Ref.

Shelf Depth

Ref. of Comb. Chamber

V

14” (356 mm)

A

18” (457 mm)

W

12” (305 mm)

B

16” (406 mm)

X

10” (254 mm)

C

14” (356 mm)

Y

8” (203 mm)

D

12” (305 mm)

Z

1¹⁄₂” (38 mm)

E

8”

(203 mm)

Fig. 4a Combustible mantel minimum installation.

A B C D E

V

W

X

Y

Z

Fireplace

CFM146

DV Mantel Chart

7/5/01 sta

Bottom of Door Trim

Top of Combustion

Chamber

CFM146a

Y

E

A

B

C

D

F

Y

B

X

LU584-1

Locating unit

2/4/99 djt

A) Flat on wall

B) Cross corner

C) **Island

D) *Room divider E) *Flat on wall corner

F) Chase installation

Y) 6” minimum

Note (Fig. 1):
** Island (C) and Room Divider (D) installation is possible as long as
the horizontal portion of the vent system (X) does not exceed 20’ (610
cm). See details in Venting Section.
* When you install your fireplace in(D) Room divider or (E) Flat on
wall corner positions (Y), a minimum of 0” (0mm) clearance must be
maintained from the perpendicular wall and the front of the fireplace.

Fig. 1 Locating Gas Fireplace

LU584-1

Locating Your Fireplace