Dvbr series direct vent gas fireplace, Below grade installation, Vertical through-the-roof applications – Vermont Casting DVBR42 User Manual

Page 19

Advertising
background image

19

DVBR Series Direct Vent Gas Fireplace

20000584

Do not back fill around snorkel.
A clearance of at least 4” must be main-
tained between the snorkel and the soil.

If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fas-
ten brackets to wall first, then secure to snorkel with self
drilling #8 x 1/2 sheet metal screws. It will be necessary
to extend vent pipes out as far as the protruding wall
face. (Fig. 38)

Below Grade Installation

When it is not possible to meet the required vent terminal
clearances of 12” (305 mm) above grade level, a snorkel
kit is recommended. It allows installation depth down
to 7” (178 mm) below grade level. The 7” (178 mm) is
measured from the center of the horizontal vent pipe as it
penetrates through the wall.
Ensure the sidewall venting clearances are ob-
served. If venting system is installed below ground,
we recommend a window well with adequate and
proper drainage to be installed around the termina-
tion area.
If installing a snorkel, a minimum 24” (610 mm) vertical
rise is necessary. The maximum horizontal run with the
24” vertical pipe is 36” (914 mm). This measurement
is taken from the collar of the fireplace (or transition
elbow) to the face of the exterior wall. See the Sidewall
Venting Graph for extended horizontal run if the vertical
exceeds 24” (610 mm).
1. Establish vent hole through the wall (Fig. 31)
2. Remove soil to a depth of approximately 16”

(406mm) below base of snorkel. Install drain pipe.
Install window well (not supplied). Refill hole with 12”
(305mm) of coarse gravel leaving a clearance of ap-
proximately 4” (102 mm) below snorkel. (Fig. 37)

3. Install vent system.
4. Ensure a watertight seal is made around the vent

pipe coming through the wall.

5. Apply high temperature sealant caulking (supplied)

around the 4” and 7” snorkel collars.

6. Slide the snorkel into the vent pipes and secure to

the wall.

7. Level the soil so as to maintain a 4” (102 mm) clear-

ance below snorkel. (Fig. 37)

BG400

Below grade installation

2/10/99 djt

10/19/99 added standoffs

Fig. 37 Below grade installation.

Zero Clearance
Sleeve if Required

Firestop

7” Pipe

7DVSK (Snor-

kel)

4” Clearance

Min.

Window
Well

Gravel

Drain

Foundation Wall

* A minimum of 24” (608
mm) vertical pipe must be
installed when using the
7TDVSKS kit.

BG400

BG401

Snorkel

2/10/99 djt

Foundation Recess

Snorkel

Watertight Seal

Around Pipe

Wall Screws

Sheet Metal
Screws

BG401

Fig. 38 Snorkel installation, recessed foundation.

Vertical Through-the-Roof Applications

This gas fireplace has been approved for:

Vertical installations up to 40’ (12m) in height. Up
to a 10’ (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90°
elbows. (Fig. 41)

Up to two 45° elbows may be used within the hori-
zontal run. For each 45° elbow used on the horizon-
tal plane, the maximum horizontal length must be
reduced by 18” (450mm).

Example: Maximum horizontal length:

No elbows

= 10’ (3 m)

1 x 45° elbow = 8.5’ (2.6 m)

2 x 45° elbows = 7’ (2.1 m)

A minimum of an 8’ (2.5 m) vertical rise is required.

Two sets of 45° elbow offsets may be used within the
vertical sections. From 0 to a maximum of 8’ (2.5 m)
of vent pipe can be used between elbows. (Fig. 42)

7DVCS supports offsets. (Fig. 44) This application
will require that you first determine the roof pitch
and use the appropriate starter kit. (Refer to Venting
Components List)

The maximum angular variation allowed in the sys-
tem is 270°. (Fig. 42)

The minimum height of the vent above the highest
point of penetration through the roof is 2’ (610mm).
(Fig. 45) Refer to Note 2, Page 11.

Advertising