Dvbr series direct vent gas fireplace – Vermont Casting DVBR42 User Manual

Page 16

Advertising
background image

16

DVBR Series Direct Vent Gas Fireplace

20000584

V584-201

Horizontal Run

2/99 djt

10’

(254cm)

7’

(178cm)

8’

(244cm)

A

B

A + B = 17’ Max.

V584-201

Fig. 29 Maximum vent run with elbows.

In Figure 28 & 29, dimension A plus B must not be
greater than 17’ (5.2m)

The maximum number of 45° elbows permitted per
side wall installation is two (2). These elbows can be
installed in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run,
the length of the horizontal run MUST be reduced by
18” (457mm). This does not apply if the 45° elbows
are installed on the vertical part of the vent system.

The maximum number of elbow degrees in a system
is 270°. (Fig. 30)

Example:

Elbow 1

=

90°

Elbow 2

=

45°

Elbow 3

=

45°

Elbow 4

=

90°

Total angular variation =

270°

1
2
3
4

1
2
3
4

1 + 2 + 3 + 4 = 270°

FP1180

Fig. 30 Maximum elbow usage.

3 x 90°

Elbows

3 x 90°

Elbows

FP1176

Fig. 26 Maximum three (3) 90° elbows per installation.

Max 20"

Max 20"

36"

(914mm)

Max.

36"

(914mm)

Max.

FP1177

Fig. 27 Maximum horizontal runwith no rise.

7'6"

A

B

90o

A + B = 17' (Max.)

FP1178

Fig. 28 Horizontal run reduction.

If a 90° elbow is used in the horizontal vent run
(level height maintained) the horizontal vent length
is reduced by 36” (914mm). (Fig. 28, 29) This does
not apply if the 90° elbows are used to increase or
redirect a vertical rise. (Fig. 26)

Example: According to the vent graph (Page 15) the
maximum horizontal vent length in a system with a
7¹⁄₂” (191mm) rise is 20” (508mm) and if a 90° elbow is
required in the horizontal vent it must be reduced to 17’
(5.2m).