Dvbr series direct vent gas fireplace, Step 4, Rear wall vent installations - flex vent pipe – Vermont Casting DVBR42 User Manual

Page 15: Step 3, Vertical sidewall applications

Advertising
background image

15

DVBR Series Direct Vent Gas Fireplace

20000584

FP1005

Side View Vent Termination

1/25/00 djt

Finished
Wall

Vent
Termination

Fig. 23 Side view of final unit location, twist lock pipe.

FP1005

These ends should

be even

These ends

screwed to appli-

ance

1/2" (13mm)

12" (305mm)

FP1472

rise in length

4/04 djt

FP1472

Fig. 25 There must be a 1” rise in 24” length.

Install the 7” vent pipe in the same manner as Step 2.
NOTE: There must be a 1” (25 mm) rise in 24”
(610 mm) length of flex vent.

Step 4

Assemble the flex vent to the collars on the termination
as you did on the appliance.

Rear Wall Vent Installations -

Flex Vent Pipe

Follow Steps 1 and 2 on Page 14.

Step 3

Install the 4” (102 mm) flex vent pipe to the appliance
collars described in “General Information Assembling
Vent Pipes”, Page 12. If the installation requires a 45°
angle, grasp the vent pipe close to the appliance collar
and bend to 45°. DO NOT exceed 45°. (Fig. 24)

FP1473

corner flex install

4/04 djt

Termination

Flex Section

Appliance Collars

FP1473

Fig. 24 Grasp the vent pipe close to the collar and bend to
45° angle. Do not exceed 45°.

Vertical Sidewall Applications

Since it is very important that the venting system
maintain its balance between the combustion air
intake and the flue gas exhaust, certain limitations
as to vent configurations apply and must be strictly
adhered to.
The Vent Graph, showing the relationship between ver-
tical and horizontal side wall venting, will help to deter-
mine the various dimensions allowable.
Minimum clearance between vent pipes and com-
bustible materials is 1” (25 mm) on top, bottom and
sides unless otherwise noted.
When vent termination exits through foundations less
than 20” (508mm) below siding outcrop, the vent pipe
must flush up with the siding.
It is best to locate the fireplace in such a way that mini-
mizes the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent
pipe from the flue collar of the fireplace (or the top of
the Transition Elbow) to the face of the outer wall.
Horizontal plane means no vertical rise exists on this
portion of the vent assembly.

When installing the appliance as a rear
vent unit, the 90° or 45° Transition Elbow
attached directly to the rear of the unit is
NOT INCLUDED in the following criteria
and calculations, and unless specifically
mentioned should be ignored when calcu-
lating venting layouts.

The maximum number of 90° elbows per side wall
installation is three (3). (Fig. 26)

If a 90° elbow is fitted directly on top of the fireplace
flange the maximum horizontal vent run before the
termination or a vertical rise is 36” (914mm). (Fig.
27)

Advertising