24

TROUBLESHOOTING

If the unit does not operate in the cooling mode, check

the following:

• The thermostat is operating properly

• Electrical power to the unit is turned on

• The filters are not dirty

• The service doors are in place

• The 5 amp fuse is operational

If the unit does not operate in the heating mode, check

the following:

• The thermostat is operating properly

• Electrical power to the unit is turned on

• The filters are not dirty

• The gas is turned on and the manual shut-off valve

is open

• The service doors are in place

• The flame roll-out control is closed

• The diagnostic codes listed in Table 7 or on the

wiring diagrams (Figures 14 - 17, pages 31 - 34).

• The 5 amp fuse is operational

Table 8. Ignition / blower Control Diagnostic Codes

SYSTEM STATUS - IGNITION

LED STATUS

(RED)

Power On (Normal Operation)

ON

High Limit Circuit Open

1 Flash

Pressure Switch Open with Inducer On

2 Flashes

Pressure Switch Closed with Inducer Off

3 Flashes

Failed Ignition (5 attempts) - Control in 1 Hour Lockout

4 Flashes

208-230 Volt Polarity Issue

5 Flashes

Excess High limit trips (5) within one call for heat

6 Flashes

Excess pressure switch cycles (5) within one call for heat

7 Flashes

Excess flame dropouts (5) within one call for heat

8 Flashes

Not Used

9 Flashes

Flame present with gas valve Off

10 Flashes

SYSTEM STATUS - 2nd STAGE HEAT DEMAND

LED STATUS

(gREEN)

No demand for 2nd stage heat

OFF

2nd stage heat demand (Normal operation)

ON

2nd stage heat demand, high pressure switch not closed

Flashing

SYSTEM STATUS - HI/LO DEHUMIDIFY

(Cooling Mode only)

LED STATUS

(gREEN)

Factory jumper wire “R” to “DEHUM” in place or “Close
on Fall” humidistat (Low humidity) - Closed

ON

Humidistat open (High Humidity) Low Speed Blower call

OFF

SYSTEM STATUS - CFM

LED STATUS

(YELLOW)

NOT USED

OFF

Cleaning of burners

If the burners require cleaning, follow the steps below.
1. Shut off the gas supply to the unit either at the meter

or at a manual valve in the supply piping.

2. Turn off all power to the unit and set the thermostat to

the lowest temperature setting.

3. Remove the louvered control access panel from the

unit.

4. Turn the gas control knob to the OFF position. See

Figure 12 (page 29) for gas valve shut off instructions.

5. Disconnect the wires from the gas valve, ignitor, and

flame sensor.

CAUTION:

To prevent damage to the unit or internal
components, it is recommended that two
wrenches be used when loosening or tightening
nuts. Do not over tighten!

6. Using two wrenches, separate the ground-joint union

in the gas supply piping at the unit.

7. Remove the piping between the gas valve and the

ground-joint union (if applicable).

8. Remove all screws securing the burner assembly to

the furnace.

9. Carefully remove the burner assembly from the furnace.

DO NOT DAMAGE THE IGNITER WHILE REMOVING
THE BURNER ASSEMBLY.

10. Inspect the burners for accumulated dust or debris.

If necessary carefully clean them with a soft wire
brush and a vacuum cleaner. DO NOT DAMAGE THE
IGNITER WHILE CLEANING THE BURNER.

11. Replace all the parts in reverse order from which they

were removed.

12. Follow the lighting instructions found on the lower unit

door to return the unit to operation.

13. Verify proper operation after servicing.