Reznor PDF2SF Unit Installation Manual User Manual

Page 36

Advertising
background image

36

Status LED

Status LED Description

Status LED Troubleshooting Information

ALERT

Flash Code 3

(Yellow LED)

Short Cycling / Compressor
is running only briefly

Thermostat demand signal is intermittent

Low line voltage (contact utility if voltage at disconnect is low)

Excessive liquid refrigerant in compressor

Compressor bearings are seized

ALERT

Flash Code 4

(Yellow LED)

Locked Rotor

Run capacitor has failed

Low line voltage (contact utility if voltage at disconnect is low)

Check wiring connections

Excessive liquid refrigerant in compressor

Compressor bearings are seized

Measure compressor oil level

ALERT

Flash Code 5

(Yellow LED)

Open Circuit

Outdoor unit power disconnect is open

Compressor circuit breaker or fuse(s) is open

Compressor contactor has failed open

Check compressor contactor wiring and connectors

Check for compressor contactor failure (burned, pitted or open)
Check wiring and connectors between supply and compressor
Check for low pilot voltage at compressor contactor coil
High pressure switch is open and requires manual reset

Open circuit in compressor supply wiring or connections

Unusually long compressor protector reset time due to extreme
ambient temperature

Compressor windings are damaged
Check compressor motor winding resistance

ALERT

Flash Code 6

(Yellow LED)

Open Start Circuit
Current only in run circuit

Run capacitor has failed

Open circuit in compressor start wiring or connections
Check wiring and connectors between supply and the

compressor S terminal

Compressor start winding is damaged
Check compressor motor winding resistance

ALERT

Flash Code 7

(Yellow LED)

Open run circuit
Current only in start circuit

Open circuit in compressor run wiring or connections
Check wiring and connectors between supply and the

compressor R terminal

Compressor run winding is damaged
Check compressor motor winding resistance

ALERT

Flash Code 8

(Yellow LED)

Welded Contactor
Compressor always runs

Compressor contactor has failed closed

Thermostat demand signal not connected to module

ALERT

Flash Code 9

(Yellow LED)

Low Voltage
Control circuit < 17VAC

Control circuit transformer is overloaded

Low line voltage (contact utility if voltage at disconnect is low)

Check wiring connections

* Flash code number corresponds to a number of LED flashes, followed by a pause and then repeated. Trip and

alert LED’s flashing at same time means control circuit voltage is too low for operation.

Table 15. LED Diagnostics - Continued