Reznor PDF2SF Unit Installation Manual User Manual

Page 35

Advertising
background image

35

Status LED

Status LED Description

Status LED Troubleshooting Information

POWER

(Green LED)

Module has power

Supply voltage is present at module terminals

TRIP

(Red LED)

Thermostat demand signal Y
is present, but compressor is
not running

Compressor protector is open

Check for high head pressure

Check compressor supply voltage

Outdoor unit power disconnect is open

Compressor circuit breaker or fuse(s) is open

Broken wire or connector is not making contact

Low pressure switch open if present in system

Compressor contactor has failed open

ALERT

Flash Code 1

(Yellow LED)

Long Run Time Compressor
is running extremely long run
cycles

Low refrigerant charge

Evaporator blower is not running

Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or blockage
Check evaporator blower wiring and connectors
Check indoor blower control board
Check thermostat wiring for open circuit

Evaporator coil is frozen

Check for low suction pressure
Check for excessively low thermostat setting
Check evaporator airflow (coil blockages or return air filter)
Check ductwork or registers for blockage

Faulty metering device

Check TXV bulb installation (size, location and contact)
Check if TXV/fixed orifice is stuck closed or defective

Condenser coil is dirty

Liquid line restriction (filter drier blocked if present in system)

Thermostat is malfunctioning

Solenoid plug not connected
Y2 not wired at Comfort Alert
Check thermostat sub-base or wiring for short circuit
Check thermostat installation (location, level)

Comfort Alert failure

ALERT

Flash Code 2

(Yellow LED)

System Pressure Trip

High head pressure

Check high pressure switch if present in system
Check if system is overcharged with refrigerant
Check for non-condensable in system

Discharge or suction

Condenser coil poor air circulation (dirty, blocked, damaged)

Pressure out of limits

Condenser fan is not running

Check fan capacitor
Check fan wiring and connectors
Check fan motor for failure or blockage

Compressor overloaded

Return air duct has substantial leakage

If low pressure switch present in system, check Flash Code 1
information

Table 15. LED Diagnostics