Airflow information – Reznor PDF2SF Unit Installation Manual User Manual

Page 27

Advertising
background image

27

AIRFLOW INFORMATION

Table 12. Airflow Settings (CFM) & Rise (° F) for Heating Operation Mode

Table 11. Airflow Settings for Cooling

Table 10. Nominal Airflow Rates & Temperature Rises (° F)

Model Number

Heating Input

(btuh)

Heating Output

(btuh)

CFM Range

Heating Rise

Range (°F)

Cooling Output

(btuh)

Blower

Size

Motor

(HP)

X24K080CA

80,000

64,000

1100 - 1350

35-65

24,000

10 X 10

1/2

52,000

41,600

750 - 1050

X36K100CA

100,000

80,000

1200 - 1600

40-70

35,000

10 X 10

1/2

65,000

52,000

900 - 1200

X48K120CA

120,000

96,000

1350 - 2000

40-70

46,000

11 X 10

1

78,000

62,400

950 - 1300

X60K120CA

120,000

96,000

1350 - 2000

40-70

55,500

11 X 10

1

78,000

62,400

950 - 1300

NOTE: CFM and Rise are independent of ESP in a variable speed blower.

2 TON UNITS

3 TON UNITS

4 - 5 TON UNITS

BLOWER

SELECTOR

SETTING

RECOMMENDED

A/C AIRFLOW

RATE (CFM)

BLOWER

SELECTOR

SETTING

RECOMMENDED

A/C AIRFLOW

RATE (CFM)

BLOWER

SELECTOR

SETTING

RECOMMENDED

A/C AIRFLOW

RATE (CFM)

COOL

ADJUST

COOL

ADJUST

COOL

ADJUST

TAP “A”

-10%

2
T

O
N

685

TAP “A”

-10%

840

TAP “A”

-10%

4
T

O
N

1485

Normal

760

Normal

3
T

O
N

930

Normal

5
T

O
N

1650

+10%

835

+10%

1025

+10%

1815

TAP “b”

-10%

840

TAP “b”

-10%

975

TAP “b”

-10%

1620

Normal

930

Normal

1080

Normal

1800

+10%

1025

+10%

1190

+10%

1980

TAP “C”

-10%

975

TAP “C”

-10%

1110

TAP “C”

-10%

1665

Normal

1080

Normal

1230

Normal

1850

+10%

1190

+10%

1350

+10%

2035

TAP “D”

-10%

1110

TAP “D”

-10%

1290

TAP “D”

-10%

1800

Normal

1230

Normal

1430

Normal

2000

+10%

1350

+10%

1575

+10%

2200

Blower HEAT

Selector Setting

2 TON

3 TON

4 & 5 TON

Low Input

High Input

Low Input

High Input

Low Input

High Input

52,000

80,000

65,000

100,000

78,000

120,000

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

TAP “A”

750

51

1100

55

900

53

1200

63

950

61

1350

67

TAP “B”

850

45

1150

53

1000

48

1300

58

1050

55

1500

61

TAP “C”

950

41

1250

49

1100

44

1400

54

1150

50

1700

54

TAP “D”

1050

37

1350

45

1200

40

1600

47

1300

44

2000

46

NOTES:

1. Recommended temperature rises are highlighted in

bold

. Use of any other setting may result in nuisance trips.

2. Temperature rises in the table are approximate. Actual temperature rises may vary.

3. blower “ADJUST” tap non-functional in Heating mode.