│ Installation and Operation Instructions

CHS Series

68

Table 15-1 Troubleshooting Chart

PROBLEM

POSSIBLE CAUSE

CORRECTIVE ACTION

Fowled or faulty flame sensor

Inspect flame sensor for cracks of fowling, clean
or replace as necessary.

Lockout 173 - Pilot relay
feedback incorrect

Lockout 174 – Safety relay
feedback incorrect

External Electrical Noise

Look for sources of electrical noise, i.e. a large
motor or multiple pieces of equipment starting at
the same time.

Failing Limit Switch in ILK circuit

Check operation of internal LWCO, and/or
external limit (i.e. devise connected between “R”
and “LIM”); replace as necessary

Hardware failure of Sola controller

Reset power, If problem persists replace Sola
controller.

Alert 206 – Lead Lag header
temperature was invalid

System Sensor not connected

If desired, install System Sensor and wire to
SENSOR input connections “SYSTEM” and
“COM”. Otherwise ignore Alert 206

Alert 233 – Lead Lag outdoor
temperature was invalid

See Alert 248

Alert 248 – CH outdoor
temperature was invalid

Outdoor sensor not connected

The CHS is factory set with Outdoor Reset
enabled. Connect outdoor sensor or disable
Outdoor Reset.

Outdoor sensor wiring

Check wiring of outdoor sensor. Wires should
connect to SENSOR inputs “OUTDOOR” and
“COM”.

Faulty sensor

Check sensor. Should be free of ice and snow.
Check resistance of sensor and compare to
thermistor resistance chart, see Table 15-2.

Alert 448 – Flame too low

See Lockout 138

Alert 449 – Modulation rate
was limited due to flame
strength

Normal operation

Indicates

that

the

minimum

permissible

modulation rate was temporarily increased due to
low flame signal strength. If Alert persists, refer
to Lockout 138.

Inoperative CH and/or DHW
pump

Blown fuse

Check Fuse

"

B

"

.

Faulty Sola controller

If Fuse “B” not blown, and Sola controller is
operating, navigate to pump diagnostic on display.
Manually switch pump on, check for 120VAC at
pump connection terminal on line voltage barrier
strip. If 120VAC not detected, replace Sola
controller.

Faulty pump

If 120VAC supplied to pump, and pump does not
operate, replace pump.

Blower operating at high
speed while burner is off

Blower signal cable disconnected

Verify that the 5-position Molex connector on

the wiring harness is securely connected to its
mating connector on the blower.

Check that the 4-position Molex connector on

wiring harness is securely connected to its
mating connector on the Sola controller.

No 24VAC to Sola controller

Check Power LED on Sola controller.

Check Fuse

"

C

"

.

With an AC voltmeter measure voltage at

terminals J8 1 & 2, 24VAC should be present.

Blower not operating

Blower power disconnected

Verify that the 3-position Molex connector on the
wiring harness is securely connected to its mating
connector on the blower.