Slant fin corp – Slant/Fin CHS-399 User Manual

Page 72

Advertising
background image

Slant Fin Corp.

│ Installation and Operation Instructions

CHS Series

72

Table 15-3 Hold and Lockout Codes

Code

Description

Note

127

Low fire switch stuck ON

Hold

128

Fan speed failed during pre-purge

Hold / Lockout

129

Fan speed failed during pre-ignition

Hold / Lockout

130

Fan speed failed during ignition

Hold / Lockout

131

Fan movement detected during standby

Hold

132

Fan speed failed during run

Hold

133-135

RESERVED

136

Interrupted Airflow Switch failed to close

Hold

137

ILK failed to close

Hold

138

Flame too low

Lockout

139-142

RESERVED

143

Internal fault: Flame bias out of range 1

Lockout

144

Internal fault: Flame bias out of range 2

Lockout

145

Internal fault: Flame bias out of range 3

Lockout

146

Internal fault: Flame bias out of range 4

Lockout

147

Internal fault: Flame bias out of range 5

Lockout

148

Internal fault: Flame bias out of range 6

Lockout

149

Flame detected

Hold / Lockout

150

Flame not detected

Hold

151

High fire switch ON

Hold / Lockout

152

Combustion pressure ON

Hold / Lockout

153

Combustion pressure OFF

Hold / Lockout

154

Purge fan switch ON

Hold / Lockout

155

Purge fan switch OFF

Hold / Lockout

156

Combustion pressure and Flame ON

Hold / Lockout

157

Combustion pressure and Flame OFF

Lockout

158

Main valve ON

Lockout

159

Main valve OFF

Lockout

160

Ignition ON

Lockout

161

Ignition OFF

Lockout

162

Pilot valve ON

Lockout

163

Pilot valve OFF

Lockout

164

Block intake ON

Lockout

165

Block intake OFF

Lockout

166-168

RESERVED

169

Safety opto bad in test state

Lockout

170

Safety relay opto feedback incorrect

Lockout

171

Safety relay feedback incorrect in run

Lockout

172

Main relay feedback incorrect

Lockout

173

Pilot relay feedback incorrect

Lockout

174

Safety relay feedback incorrect

Lockout

175

Safety relay open

Lockout

176

Main relay ON at safe start check

Lockout

177

Pilot relay ON at safe start check

Lockout

178

Safety relay ON at safe start check

Lockout

179-180

RESERVED

181

Invalid Blocked condensate enable setting

Disabled

182

Invalid J7-1 configuration, both LFS and Blocked condensate

Disabled

183

Invalid J7-2 configuration, both HFS and Flap valve

Disabled