Slant Fin Corp.

22

Annual Inspection Checklist
The Slant/Fin CHS 300-399 Common Venting must be inspected at the beginning of every heating season by a
Qualified Technician.

 1. For each boiler perform the Annual Inspection Checklist in the boiler Installation and Operation

Instructions.

 2. Inspect the CHS 300-399 Common Venting termination components for damages caused by exposure to

weather elements. If termination components are damaged or worn have the parts removed and
replaced.

 3. Examine the termination Bird Screens for debris.

 4. Examine all venting for evidence of leaks. If a leak is found repair or replace the part.

 5. Look for condensate or debris in the Non-Return Valves, if found remove and clean them.

 6. Examine the support clamps for rigidity; tighten if loose or replace if damaged.

 7. Check the Connector Rings for a secure lock between each connection.

 8. Conduct a visual inspection to ensure the CHS 300-399 Common Venting is adequately sloped and not

sagging.

 9. Confirm there is nothing obstructing the flow of the Combustion Air-Inlet and Exhaust Gases.

 10. Keep boiler area clear and free from combustible materials, gasoline, and other flammable vapors and

liquids.


Failure to properly inspect each joint fitting in the CHS 300-399 Common Venting may
result in flue gas leakage causing serious injury or death.