CHS Series CHS 300-399 Common Venting

Slant Fin Corp.

9

4.0

COMMON VENT MANIFOLD SYSTEM ASSEMBLY INSTRUCTIONS

Before commencing the assembly of the CHS 300-399 Common Venting, identify which direction to direct the
Exhaust Gas and Combustion Air-Inlet piping. The direction will dictate the length the branches need to be cut
to.




Figure 4-1 Piping to the LEFT


















Branch 6” x 4” –
when directing the exhaust gas and combustion air-inlet piping to the LEFT, the overall length
of the branches must be reduced to the lengths indicated in Figure 4-1; 18” and 40” for the right side Combustion
Air-Inlet and Exhaust Gas outlet respectively, 33” for the others.
NOTE: This only applies to P/N 818 192 and P/N 818 193 being piped to the LEFT.

Figure 4-2 Piping to the RIGHT


















Branch 6” x 4” – when directing the Exhaust Gas and Combustion Air-Inlet piping to the RIGHT, the overall
length of the branches must be reduced to the length indicated in Figure 4-2; 33” for each Branch.
NOTE: This only applies to P/N 818 192 and P/N 818 193 being piped to the RIGHT.

See Figures Below

Exhaust
Manifold

Air-Inlet
Manifold

Exhaust
Gas

Combustion
Air-Inlet

3/8” per foot
Slope

33

40

18

Combustion
Air-Inlet

Exhaust
Gas

All Branches = 33

3/8” per
foot Slope

Air-Inlet
Manifold

Exhaust
Manifold