CHS Series CHS 300-399 Common Venting

Slant Fin Corp.

5

Table 2-3 Acceptable CHS Common Vent and Termination Parts

1

DESCRIPTION

PART No.

COMMENTS

IMAGE

Elbow 6”

2

818 205 (45° Elbow)

818 206 (87 ° Elbow)

-

Straight Pipe Length 6”

3

818 194 (6” x 12”)
818 195 (6” x 24”)
818 196 (6” x 36”)
818 197 (6” x 72”)

-

Connector Ring 6”

4

818 198

Mandatory at every
connection.

Support Clamps 6”

5

818 199

Mandatory every 75” spaced
on vertical runs and every
40” on horizontal runs.

Bird Screen PPs-UV 6”

818 200

PPs-UV Components must
be used for the vent
termination or any area
where the venting is exposed
to sunlight.

Note: Only Centrotherm –
InnoFlue PPs-UV parts are
approved for terminating the
Common Vent System.

End Pipe PPs-UV

818 201 (6” x 20”)
818 202 (6” x 39”)

Elbow PPs-UV 6”

818 203 (87° Elbow)

Elbow PPs-UV 6”

818 204 (45 ° Elbow)

Straight Vent Length
PPs-UV

818 207 (6” x 26.5”)

Notes:

1

With the exception of the CHS Common Venting, the installer is responsible for supplying all the required venting components;

including pipe lengths, termination, Connector Rings, and Support Clamps.

2

When determining the maximum vent lengths each 6” diameter Elbow (87° and 45°) are equivalent to 5 feet of pipe length.

3

The total maximum equivalent vent length for each Exhaust and Air-Inlet is 100 feet.

4

Connector Rings are required on every connection.

5

Support Clamps are required every 75” for vertical runs and every 40” for horizontal runs.

Consult Centrotherm – InnoFlue Eco Systems (1-877-434-3432 or www.centrotherm.us.com) instructions for further details.