BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY

† Head settings shown are approximate ONLY. See “START-UP” on page 8.

NOTES:
(1) Insertion depth is 4.5".
(2) See “PRECAUTIONS BEFORE STARTING OIL BURNERS” and “START-UP” on page 8 and burner figures on this page.
(3) All burner models shown are single stage.

Boiler

Model

Burner

Model

Blast

Tube

Firing

Rate

GPH

Nozzles

Oil Pump

(PSIG)

Head

Adjusting

Plate †

Approx.

Air Band

Setting

Shutter

Non-

Adjustable

Size

GPH

Angle &

Type

MFR.

EC-13

EZ-1HP

7" Long

0.65

0.5

45˚A

Delavan

170

.60/.65

0.53

Blank

0.7

0.5

45˚A

Delavan

195

.60/.65

0.55

Blank

EC-14

EZ-1HP

7" Long

0.8

0.65

60˚B

Delavan

150

.60/.65

0.6

Blank

0.9

0.75

60˚B

Delavan

145

0.75

0.65

Blank

EC-15

EZ-1HP

7" Long

1

0.85

60˚B

Delavan

138

.85/1.00

0.75

Blank

1.1

0.85

60˚B

Delavan

168

.85/1.00

0.85

Blank

EC-16

EZ-1HP

7" Long

1.15

0.85

60˚B

Delavan

185

.85/1.00

0.9

Blank

1.25

1

60˚B

Delavan

155

1.10/1.25

0.9

Blank

Figure 5. Electrode placement, retention ring assembly and nozzle adapter.

Figure 6. Installing head positioning bar.

It is suggested that due to the positive pressure observed in the chamber that the air tube hole and any other passages of the flue gas
leakages be sealed to avoid combustion gas fumes from leaking into the boiler room.

EUTECTIC EC-10

17