Slant/Fin EC-10 Installation User Manual

Page 2

Advertising
background image

EUTECTIC EC-10

2

Maximum operating pressure 60 psi.
All boilers hydrostatically tested — A.S.M.E.
* For forced hot water heating systems where the boiler and all piping are

located within the area to be heated, the boiler may be selected on the basis
of D.O.E. capacity output. The net AHRI output ratings shown are based on
an allowance for piping and pickup of 1.15 (water). D.O.E. capacity output is
divided by the allowance to obtain net rating. The Slant/Fin Technical Service
department should be consulted before selecting a boiler for unusual piping
and pickup requirements such as intermittent system operation, extensive
piping, etc.

† Ratings apply to the use of light oil at 140,000 Btu per gallon and apply only

when burner models listed on pages 13 and 17 of this manual are used, and

are properly adjusted to produce 13% CO2.

§ Boiler models have two firing rates. The boiler is factory shipped at the lower

firing rate. To obtain the higher firing rate, refer to the boiler installation
instructions for the appropriate field adjustments.

# All dimensions subject to normal manufacturing tolerance.
NOTE: All boilers under 300,000 Btuh (87.9 kw) input are tested and rated for
capacity under the U.S. Department of Energy (D.O.E.) Test Procedures for
Boilers.

TABLE 1: Ratings and Dimensions

EC-13P

0.65

91,000

79

69

6 x 15

87

36

22-1/4

27

5

11-13/16

2

EC-13-0.7

0.70

98,000

85

74

6 x 15

86

36

22-1/4

27

5

11-13/16

2

EC-14P

0.80

112,000

98

85

6 x 15

87

41

27-1/4

32

5

16-13/16

2

EC-14-0.9

0.90

126,000

109

95

6 x 15

86

41

27-1/4

32

5

16-13/16

2

EC-15P

1.00

140,000

123

107

6 x 15

87

46

32-1/4

37

5

21-13/16

2

EC-15-1.1

1.10

154,000

134

117

6 x 15

86

46

32-1/4

37

5

21-13/16

2

EC-16P

1.15

161,000

141

123

6 x 15

87

51

37-1/4

42

6

26-13/16

4

EC-16-1.25

1.25

175,000

152

132

6 x 15

86

51

37-1/4

42

6

26-13/16

4

BOILER

MODEL

NO.

GPH

BTUH

AHRI

BURNER

CAPACITY

OIL INPUT † §

D.O.E.

HEATING

CAPACITY

MBH *

WATER

APPROX.

OVERALL

LENGTH

“A”

AHRI

WATER

NET

RATING

MBH *

AHRI

CHIMNEY SIZE

DIMENSIONS (inches) #

I.D. ROUND

X HEIGHT

(in x ft)

AFUE %

BOILER

LENGTH

“B”

BOILER

LENGTH

“C”

FLUE

DIA.

“D”

DISTANCE
BETWEEN

LEGS

“E”

FLUE

OUTLET

LENGTH

“F”

Figure 1: Dimensions

1-1/4 threaded

supply

Flue outlet øD

1-1/4 threaded
return pipe

Drain outlet

Relief valve 3/4’’

Supply Pipe Mounted

Tridicator

Panel Mounted
Tridicator Pressure
Sensor Well

Panel Mounted
Tridicator Temperature
Sensor Well

A