EUTECTIC EC-10
4
Sufficient space shall be left clear around the boiler.
the minimum recommended dimensions for providing
easy access around the boiler.
8578N016
20
A
40
22
7/
16
20
20
33
7/8
Boiler A
(in)
EC-13
22
1/4
1/4
EC-14
27
EC-15
32
1/4
EC-16
37
1/4
EC-10
Do not stack items on or box in the appliance within
the required clearances to combustibles.
The figures stated in inches in the drawing below are
CHIMNEY
BOILER
BOILER
PITCH UP
1/4" PER LINEAR FOOT
DO NOT INSTALL DRAFT REGULATOR HERE
BAROMETRIC DRAFT CONTROL
INSTALLED ON VERTICAL RISE
18"
MINIMUM
9"
PITCH UP
1/4" PER
LINEAR FOOT
DOUBLE SWING BAROMETRIC DRAFT
CONTROL INSTALLED ON HORIZONTAL
CONNECTOR
DRILL 1/4" HOLE TO MEASURE
DRAFT,SMOKE,CO % AND STACK
TEMPERATURE
DO NOT INSTALL DRAFT REGULATOR HERE
9"
18"
MINIMUM
2
DRILL 1/4" HOLE TO MEASURE
DRAFT,SMOKE,CO % AND STACK
TEMPERATURE
2
CHIMNEY
Figure 2. Barometric Draft Regulator Location