Slant/Fin EC-10 Installation User Manual

Page 21

Advertising
background image

BURNER DATA - RIELLO (continued)

REGULATION OF THE TURBULATOR AND AIR SHUTTER FOR
PROPER COMBUSTION
Turbulator Setting

1. Loosen nut, 1, then turn the screw, 2, until the index marker,
3, is aligned with the correct index number.
2. Retighten the retaining nut, 1.

TURBULATOR SETTINGS - RIELLO 40 SERIES

The numbers on the casting are there to denote the high and low
end of the scale - in all cases the first mark is “Zero”.
The air/oil ratio depends on accurate setting of the turbulator disc.
Be careful when making this adjustment as an incorrect setting will
result in an unsatisfactory installation. See figure 12A and 12B.

1. Regulation of the combustion air flow is made by adjustment

of the manual AIR ADJUSTMENT PLATE (4) after loosening
the FIXING SCREWS (3&5). The initial setting of the air
adjustment plate should be made according to figure 13.

2. The proper number on the manual AIR ADJUSTMENT PLATE

(4) should line up with the SETTING INDICATOR (2) on the
fan housing cover. Once set, the air adjustment plate should
be secured in place by tightening SCREWS 3 and 5.

3. The final position of the air adjustment plate will vary on each

installation. Use instruments to establish the proper settings for
maximum CO

2

and a smoke reading of zero.

NOTE:

Variations in flue gas, smoke, CO

2

and temperature

readings may be experienced when the burner cover is
put in place. Therefore, the burner cover MUST be in
place when making the final combustion instrument
readings, to ensure proper test results.

Figure 12A. Model F-5

Figure 12B. Model F-3

Note: For F-3 and F-5 models, the air shutter is

operated on a 120V 60 Hz. motor, the
burner will not operate until the air
shutter is in its fully open position.

Figure 13. Model F-3, F-5 Air Adjustment

SETTING THE AIR ADJUSTMENT PLATE

EUTECTIC EC-10

21

Advertising