background image

BOILER "A" "B" "C" "D"
MODEL

LX-90 6 3/4 3 3/8 2 3/4 16 1/4

LX-120 6 5/8 3 3/8 2 16 1/4

LX 150

6 3/8

3 3/4

2 3/4

19

33

35

22

LEFT SIDE FRONT RIGHT SIDE

5

"D"

"A"

"B"

"C"

Lynx

2

RATINGS AND DIMENSIONS

Figure 1. Dimensions data

SPECIFICATIONS

BOILER MODEL

LX-90

LX-120

LX-150

Input Rate, Btu/Hr

Max.

Min.

90,000
25,000

120,000

30,000

150,000

37,500

Water Piping Connection

1" NPT (Male)

Gas Piping Connection

1/2" NPT (Female)

Vent Connection

3" Nominal ID Pipe PVC, CPVC, Polypropylene

(solid or flexible) or SS. SEE WARNING

Air Intake Connection

3" Nominal ID PVC or CPVC

Gas Orifice Size for Natural Gas

No Orifice Used

Gas Orifice Size for Propane

0.1900"

Code # C

0.2025"

Code # A

0.2200"

Code # E

Boiler Water Volume

Gal.

0.4

0.6

1.1

Weight of Boiler (Uncrated)

Lbs.

118

125

140

WARNING:

1. Use of cellular core PVC and CPVC or Radel for venting system is NOT allowed

2. Thermal insulation on non-metallic vent pipe and fittings is NOT allowed.

BOILER "A" "B" "C" "D"
MODEL

LX-90 6 3/4 3 3/8 2 3/4 16 1/4

LX-120 6 5/8 3 3/8 2 16 1/4

LX-150 6 3/8 3 3/4 2 3/4 19