B. BLOCKING ERRORS:

Indicated by an “E” in the mode display. Operation is automatically restored, once the

condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset”
button is not required.

ERROR CODE

INDICATION

REMEDY

01

Water Outlet Sensor Open

Check wire harness connections going to the
sensor.
Replace the sensor.

02

Water Inlet Sensor Open

Check wire harness connections going to the
sensor.
Replace the sensor.

03

Flue Gas Sensor Open

Check wire harness connections going to the
sensor.
Replace the sensor.

11

Water Outlet Sensor Shorted

Replace the sensor.

12

Water Inlet Sensor Shorted

Replace the sensor.

13

Flue Gas Sensor Shorted

Replace the sensor.

19, 42, 45,

46, 47, 48

Control Failure

Replace control board. Make sure the proper
boiler model selection and confirmation code is
entered. See Table 5 on page 33.

20

Flame Detected at Wrong Time

If a flame is still observed after a call for heat is
stopped, replace the gas valve, If the burner
seems to be shutting down properly, replace the
spark ignitor.

21

Polarity Error

Reverse the hot and neutral power supply wires.

22

Frequency Error

Check power supply frequency to be 60 hz,
certain power supplies may not provide the
proper frequency.

24

Earth Connection Faulty

Check grounding of control and boiler chassis.

continued on page 40