IV. Check combustion and fuel input rate

A. Remove the boiler jacket front panel by turning the black

screws 1/4 turn to the open position. Lift off the panel.

B. Start and run the boiler in the “System Test” mode in the

“VIEWING AND CHANGING SYSTEM SETTING” menu.
Refer to table 5 on page 33. Use the

p

or

q

push button to

choose first the high (alternating S-H on mode display) and
then the low (alternating S-L on mode display) firing rate.

C. Check the fuel input rate on the gas meter (for natural gas

boilers).

BTUH INPUT= cu.ft. metered in 3 minutes X heating value of
the gas* X 20

*The higher heating value of the gas can vary for different
localities. Consult the gas supplier for this value in
BTU/cu.ft.

If the fuel input is not at the rate specified on page 2 at the high
or low firing rate, then the blower speed should be adjusted to
attain the specified input rate. This can be done by using the
“Change blower RPM for high or low input” mode in the
“VIEWING AND CHANGING SYSTEM SETTING” menu.
Refer to Table 5 on page 33. Increasing the blower RPM will
increase the fuel input rate, and decreasing the blower RPM
will decrease the fuel input rate.

D. Measure the CO and CO2 of the flue gas at high and low

firing rate using a calibrated combustion test instrument. A
flue sample port is provided in the vent pipe (See Figure 2
on page 3). The CO should not exceed 100 PPM at high
input and 50 PPM at low input when the combustion is
correct. The CO2 should be in the range listed in Table 6.

E. If the combustion (CO2 and CO measurement) at either

high or low input rate is out of the range, shut down the
boiler and contact Slant/Fin Tech. service department at
1-800-873-4346.

F.

Exit the “System Test” mode (Push “ENTER” button).

V. SAFETY CHECK

A. Check for gas leaks:

Using soap solution, check for gas leaks from meter to gas
valve including all pipes and fittings and gas valve
connections. Use liquid soap solution for all gas testing. DO
NOT use open flame.

B. Thermostat Test:

Set thermostat setting to low enough to end call for heat.
Gas valve should close and burner should stop firing.
Blower and circulator pump should go into a post purge,
then shut off.

C. Control Safety Shutdown test:

With the burner firing, disconnect the spark cable from the
spark ignitor. Gas valve should close and burner should
stop firing. The boiler will try for ignition three times after
this, then should lock out with an “A 01” error shown on the
display. Reconnect the spark cable to the spark ignitor, and
press the “Reset” button to return to normal operation.

Warning: Only a trained and qualified service technician must

do the adjustment to the input of the boiler.

Warning: Failure to comply with the above mentioned

requirement might result in property damage,

personal injury or loss of life.

Fuel

Firing

Rate

CO2%

Minimum

Nominal

Maximum

Natural

Gas

High

9.2%

9.5%

9.8%

Low

8.7%

9.0%

9.3%

Propane

High

10.7%

11.0%

11.3%

Low

10.2%

10.5%

10.7%

Table 6. Combustion values for natural gas and propane.