Lynx boiler sequence of operation, Lynx 36 – Slant/Fin LX-150 User Manual

Page 36

Advertising
background image

Lynx

36

LYNX BOILER SEQUENCE OF OPERATION

THERMOSTAT CALLS FOR HEAT

CIRCULATOR(S) ON

5 SECOND PRE-PURGE PERIOD

GAS VALVE REMAINS OPEN. CONTROL

CONTINUOUSLY MONITORS

THERMOSTAT, HIGH LIMIT, WATER

SENSORS, BLOWER SPEED, FLAME

SIGNAL, AND LWCO (IF USED).

THERMOSTAT CALL FOR HEAT ENDS

GAS VALVE CLOSES

10 SECOND BLOWER POST PURGE.

15 SECOND CIRCULATOR POST PURGE.

CONTROL LOCKOUT

DISPLAY SHOWS

ERROR “A 33”

YES

NO

NO

COMBUSTION BLOWER ON

(AT MEDIUM SPEED)

TRIAL FOR IGNITION

SPARK IGNITOR ENERGIZED

FOR 3.5 SECONDS

YES

GAS VALVE OPENS

FOR 2.5 SECONDS

SPARK CONTINUES FOR

2.5 SECONDS

SPARK IGNITOR DE-ENERGIZED

GAS VALVE REMAINS OPEN FOR

3.5 SECONDS

YES

2 TIMES RETRIALS

FOR IGNITION

GAS VALVE CLOSED.

BLOWER POST PURGE

10 SECONDS.

NO

CONTROL LOCKOUT

DISPLAY SHOWS

ERROR “A 01”

YES

CONTROL LOCKOUT

DISPLAY SHOWS

ERROR “A 03”

NO

WATER HIGH LIMIT

CLOSED?

BLOWER SPEED CONFIRMED?

3 TRIALS FOR

IGNITION WITH NO

FLAME SENSED?

FLAME SIGNAL SENSED?