Slant/Fin LX-150 User Manual

Page 26

Advertising
background image

Lynx

26

Table 2. Recommended pump models for domestic hot water tank piping.

Figure 19. Boiler water side pressure drop

0

0

2

4

6

8

10

12

14

2

4

6

8

10

Head
(feet w.c.)

Flow Rate (GPM)

15

LX

-1

50

L

X

-9

0

LX

-1

20

Notes:

*

This is the minimum flow rate recommended for the boiler.

**

Domestic water tank piping head is based on 1” inside diameter piping and full port valves.

***

Refer to the DHW Tank Manufacturer’s water flow rate requirements and associated pressure drop head loss, to select
the appropriate circulator.

Or Grundfos UPS 26-99F.

Boiler
Model

No.

Flow

Rate

(gpm)

Temp

Rise

(˚F)

Boiler

Head

Loss

(Feet w.c.)

Domestic

Water

Tank Piping

Head Loss **

(Feet w.c.)

Available Head Capability Left for Various

Model Circulators to Overcome DHW Tank

Head Loss (Feet w.c.) ***

Taco 0014

Taco 0011

Taco 0013

8.1

20

8.2

2.5

7.3

14.1

17.5

6.5

25

5.4

2.2

10.9

18.2

22.2

5.4

30

3.5

2.0

14.0

21.3

25.2

4.0*

40

2.1

1.5

16.4

23.9

28.2

10.8

20

9.5

3.0

4.5

11.4

13.4

8.6

25

6.6

2.7

8.5

14.8

18.7

7.2

30

4.2

2.5

11.5

18.3

22.2

5.4*

40

2.5

1.5

15.5

23.0

27.0

13.5

20

9.0

3.5

2.7

7.5

11.5

10.8

25

6.0

3.0

8.0

13.5

17.5

9.0

30

4.2

2.5

11.0

17.0

20.5

6.8*

40

2.5

2.0

14.0

21.5

24.5

LX-90

LX-120

LX-150

Advertising
This manual is related to the following products: