Tie Down Vector Dynamics Foundation System for Wind Zones lll User Manual

Page 18

Advertising
background image

D103

0

Tie Down Engineering

255 Villanova Drive SW

Atlanta, Georgia 30336

(404) 344-0000 • Fax (404) 349-0401

www.tiedown.com

Example of a Single Section 14' x 72' Home

WIND ZONE II for Single Section Homes

Using Vector Dynamics Foundation Systems

Soil Classifications:

2, 3, 4A & 4B

Soil Bearing Capacity:

1,000 PSF Minimum

Anchors Required:

30" with 2-4" helix anchors (#59095) with 1-1/4" Vertical Ties

Home Length

Vector Systems

Anchors Required

Anchors Required

Longitudinal

Required

Per Side - 6” Eave

over 6” Eave

Systems* (LSD)

0 to 48’

4

4

5

2 (4 Struts)

49’ to 60’

5

5

6

2 (4 Struts)

61’ to 72’

6

6

7

2 (4 Struts)

73’ to 84’

7

7

8

2 (4 Struts)

85’ to 90’

8

8

9

2 (4 Struts)

Vector

Systems

Longitudinal

(LSD)

Longitudinal

(LSD)

Anchors

Vector

Systems

Wind Zone II

NOTES:
Vector Systems should be spaced as symmetrical as possible along
the length of the home. Pier spacing must be consistent with home
manufacturers instruction and/or state requirements.

Maximum allowable working load for metal strut: 3150 lbs.

* One Longitudinal Vector System is made up of 2 struts,

which can be used separately.

18

Revised: 8/19/08