Tie Down Vector Dynamics Foundation System for Wind Zones lll User Manual

Page 21

Advertising
background image

D1030

Tie Down Engineering

255 Villanova Drive SW

Atlanta, Georgia 30336

(404) 344-0000 • Fax (404) 349-0401

www.tiedown.com

Example of a Single Section 14' x 62' Home

WIND ZONE III for Single Section Homes

Using Vector Dynamics Foundation Systems

Soil Classifications:

2, 3, 4A & 4B

Soil Bearing Capacity:

1,000 PSF Minimum

Anchors Required:

30" with 2-4" helix anchors (#59095) with 1-1/4" vertical ties

Vector

Systems

Longitudinal

(LSD)

Longitudinal

(LSD)

Anchors

Wind Zone III

NOTES:
Vector Systems should be spaced as symmetrical as possible along
the length of the home. Pier spacing must be consistent with home
manufacturers instruction and/or state requirements.

Maximum allowable working load for metal strut: 3150 lbs.

1

One Longitudinal Vector System is made up of 2 struts,

which can be used separately.

Home Length

Vector Systems

Anchors Required

Longitudinal

Required

Per Side

Systems

1

(LSD)

0 to 54’

6

6

2 (4 Struts)

55’ to 63’

7

7

2 (4 Struts)

64’ to 72’

8

8

2 (4 Struts)

73’ to 90’

9

9

2 (4 Struts)

21

Revised: 8/19/08