DSE Model 7000 Series Control and Instrumentation System Operators Manual

100

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

Front Panel Configuration Editor (continued)

Section

Parameter as shown on display

Factory Settings

MAINS

Mains Under Voltage Trip

184V

Mains Over Voltage Trip

276V

Mains Under Frequency Trip

45Hz

Mains Over Frequency Trip

55Hz

Mains Transient Delay

2s

Return Delay

30s

Mains Transfer Time

0.7s

TIMERS

LCD Page Timer

5m

Auto Scroll Delay

3s

Pre Heat Timer

0s

Crank Duration Timer

0s

Crank Rest Timer

10s

Safety On Delay

10s

Smoke Limiting

10s

Smoke Limiting Off

0s

Warm Up Timer

0s

Cool Down Timer

0s

Speed Overshoot Delay

1m

Fail To Stop Delay

2s

Battery voltage Low Warning Delay

30s

Battery Voltage High Warning Delay

1m

Return Delay

1m

Generator Transient Delay

30s

Mains Transient Delay

0s

Mains Transfer Time

2s

Schedule

0.7s

SCHEDULE

Schedule On Load

Active, Inactive

Schedule Period

Active, Inactive (only available when Scheduler is active)

Schedule time and Date Selection (1-16)

Weekly, Monthly, (only available when Scheduler is active

Schedule time and Date Selection (1-16)

Press

to begin editing then

or

to select the different parameters in the

scheduler.