Winco DSE7300 Series User Manual

Page 37

Advertising
background image

DSE Model 7000 Series Control & Instrumentation System Operators Manual

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

37


4.3.3 7310 AUTOSTART CONTROLLER


3 phase, 4 wire with restricted earth fault protection

NOTE:- Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults

‘after’ the CT only (Restricted to load / downstream of the CT)
Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT
only (Restricted to generator / upstream of the CT)