3 terminal specification, 4 power supply requirements, 5 generator and mains voltage / frequency sensing – Winco DSE7300 Series User Manual

Page 9

Advertising
background image

DSE Model 7000 Series Control & Instrumentation System Operators Manual

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

9

3.3 TERMINAL SPECIFICATION


Connection type

Two part connector.

Male part fitted to module

Female part supplied in module
packing case - Screw terminal,
rising clamp, no internal spring.

Example showing cable entry and screw

terminals of a 10 way connector

Minimum cable size

0.5mm² (AWG 24)

Maximum cable size

2.5mm² (AWG 10)

NOTE : For purchasing additional connector plugs from DSE, please see the section entitled

Maintenance, Spares, Repair and Servicing elsewhere in this document.


3.4 POWER SUPPLY REQUIREMENTS


Minimum supply voltage

8V continuous

Cranking dropouts

Able to survive 0V for 50mS providing the supply was at least 10V before the
dropout and recovers to 5V afterwards.
This is more than sufficient to allow the module to operate during engine
cranking where the battery supply often falls as low as 4V (on a 12V system!)

This is achieved without the need for internal batteries or other external
requirements.

Maximum supply voltage

35V continuous (60V protection for surges)

Reverse polarity protection

-35V continuous

Maximum operating current

DSE7200 / DSE7300

160mA at 24V
340mA at 12V

Maximum standby current

DSE7200 / DSE7300

80mA at 24V
160mA at 12V


Plant supply instrumentation display

Range

0V-70V DC (note Maximum continuous operating voltage of 35V DC)

Resolution

0.1V

Accuracy

±1% full scale (±0.7V)


3.5 GENERATOR AND MAINS VOLTAGE / FREQUENCY SENSING


Measurement type

True RMS conversion

Sample Rate

5KHz or better

Harmonics

Up to 10

th

or better

Input Impedance

300K

ph-N

Phase to Neutral

15V

(minimum required for sensing frequency

)

to 333V AC

(absolute maximum)

Suitable for 110V to 277V nominal

(±20% for under/overvoltage detection)

Phase to Phase

26V

(minimum required for sensing frequency

)

to 576V AC

(absolute maximum)

Suitable for 190V ph-ph to 479V ph-ph nominal

(±20% for under/overvoltage detection)

Common mode offset from Earth

100V AC (max)

Resolution

1V AC phase to neutral
2V AC phase to phase

Accuracy

±1% of full scale phase to neutral (±3.33V ph-N)
±2% of full scale phase to phase (±11.52V ph-ph)

Minimum frequency

3.5Hz

Maximum frequency

75.0Hz

Frequency resolution

0.1Hz

Frequency accuracy

±0.2Hz