Winco DSE7300 Series User Manual

Page 11

Advertising
background image

DSE Model 7000 Series Control & Instrumentation System Operators Manual

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

11


Fuel Level

Measurement type

Resistance measurement by measuring voltage across sensor with a fixed current
applied

Arrangement

Differential resistance measurement input

Measurement current

10mA

Full scale

480

Over range / fail

540

Resolution

1%

Accuracy

+/-2% of full scale resistance (±9.6

) excluding transducer error

Max common mode voltage

±2V

Display range

0-250%


Flexible Sensor

NOTE : Flexible sensor is not available on DSE7200 series controllers


Measurement type

Resistance measurement by measuring voltage across sensor with a fixed current
applied

Arrangement

Differential resistance measurement input

Measurement current

10mA

Full scale

480

Over range / fail

540

Resolution

1%

Accuracy

+/-2% of full scale resistance (±9.6

) excluding transducer error

Max common mode voltage

±2V

Display range

0-250%


3.7.3 CHARGE FAIL INPUT


Minimum voltage

0V

Maximum voltage

35V (plant supply)

Resolution

0.2V

Accuracy

± 1% of max measured voltage (±0.35V)

Excitation

Active circuit constant power output

Output Power

2.5W Nominal @12V and 24V

Current at 12V

210mA

Current at 24V

104mA

Advertising
This manual is related to the following products: