8.9 MAINTENANCE ALARM


Depending upon module configuration one or
more levels of maintenance alarm may occur
based upon a configurable schedule.
There are three maintenance alarms in the
DSE7200/DSE7300 series V3 and above, and
one level of maintenance alarm in prior versions.



Example 1

Screen capture from DSE Configuration Suite
Software showing the configuration of
Maintenance Alarm 1 and Maintenance Alarm 2.

When activated, the maintenance alarm can be
either a warning (set continues to run) or
shutdown (running the set is not possible).
Resetting the maintenance alarm is normally
actioned by the site service engineer after
performing the required maintenance.
The method of reset is either by:

Activating a input that has been configured to maintenance x reset, where x is the number of the
maintenance alarm (1 to 3).

Pressing the maintenance reset button in the DSE Configuration Suite, Maintenance section.




Example 2

Screen capture from DSE Configuration Suite
Software showing the configuration of a digital
input for Reset Maintenance Alarm 1.






Example 3

Screen capture from DSE Configuration Suite
Software showing the Maintenance Alarm Reset
‘button’ in the DSE Configuration Suite SCADA |
MAINTENANCE section.