Winco DSE7300 Series User Manual

Page 69

Advertising
background image

DSE Model 7000 Series Control & Instrumentation System Operators Manual

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

69


5.7 CONTROLS


Stop / Reset
This button places the module into its Stop/Reset mode. This will clear any alarm conditions for
which the triggering criteria have been removed. If the engine is running and the module is in Stop
mode, the module will automatically instruct the changeover device to unload the generator (‘Close
Generator
becomes inactive (if used))
. The fuel supply de-energises and the engine comes to a
standstill. Should a remote start signal be present while operating in this mode, a remote start will
not occur.

Manual
This mode allows manual control of the generator functions. Once in Manual mode the module will

respond to the start

button, start the engine, and run off load. If the engine is running off-load in

the Manual mode and a remote start signal becomes present, the module will automatically instruct
the changeover device to place the generator on load (‘Close Generator becomes active (if used)).
Upon removal of the remote start signal, the generator remains on load until either selection of the
‘STOP/RESET’ or ‘AUTO’ modes.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere in this
manual.

Auto
This button places the module into its ‘Automatic’ mode. This mode allows the module to control the
function of the generator automatically. The module will monitor the remote start input and mains
supply status and once a start request is made, the set will be automatically started and placed on
load.
Upon removal of the starting signal, the module will automatically transfer the load from the generator
and shut the set down observing the stop delay timer and cooling timer as necessary. The module will
then await the next start event. For further details, please see the more detailed description of ‘Auto
operation’ elsewhere in this manual.

5.7.1.1 TEST (DSE7220/DSE7320 ONLY)

This button places the module into its ‘Test’ mode. This allows an on load test of the generator.

Once in Test mode the module will respond to the start

button, start the engine, and run on load.

For further details, please see the more detailed description of ‘Test operation’ elsewhere in this
manual.

5.7.1.2 START

This button is only active in STOP/RESET

or MANUAL

mode.

Pressing this button in manual or test mode will start the engine and run off load (manual) or on load
(test).
Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when correctly
configured and fitted to a compatible engine ECU)

Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the LEDs as a lamp test
feature/
When correctly configured and fitted to a compatible engine ECU, pressing this button in

STOP/RESET mode after pressing the START

button (to power the ECU) will cancel any

“passive” alarms on the engine ECU.

Advertising
This manual is related to the following products: