Winco DSE7300 Series User Manual

Page 31

Advertising
background image

DSE Model 7000 Series Control & Instrumentation System Operators Manual

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

31

Connection of CT s1 terminal


PIN

No

DESCRIPTION

CABLE

SIZE

NOTES

51

CT Secondary for Gen L1

2.5mm²

AWG 13

Connect to s1 secondary of L1 monitoring CT

52

CT Secondary for Gen L2

2.5mm²

AWG 13

Connect to s1 secondary of L2 monitoring CT

53

CT Secondary for Gen L3

2.5mm²

AWG 13

Connect to s1 secondary of L3 monitoring CT

Connection to terminals 54 & 55 (DSE7200 SERIES)

Pin

No

Description

CABLE

SIZE

54

DO NOT CONNECT

55

Common for CTs connected to L1,L2,L3 (s2)

2.5mm²

AWG 13

NOTE:- Terminals 56 to 59 are not fitted to the 7200 / 7300 series controller.

NOTE:- Take care to ensure correct polarity of the CT primary as shown overleaf. If in doubt, check

with the CT supplier.


Connection to terminals 54 & 55 (DSE7300 SERIES)

The function of terminals 54 and 55 CHANGES depending upon what kind of earth fault protection (if any) is being used:

Topology

Pin

No

Description

CABLE

SIZE

No earth fault measuring

54

DO NOT CONNECT

55

Connect to s2 of the CTs connected to
L1,L2,L3,N

2.5mm²

AWG 13

Restricted earth fault measuring

54

Connect to s2 of the CTs connected to
L1,L2,L3,N

2.5mm²

AWG 13

55

Connect to s1 of the CT on the neutral
conductor

2.5mm²

AWG 13

Un-restricted earth fault measuring
(Earth fault CT is fitted in the neutral to earth
link)

54

Connect to s1 of the CT on the neutral to
earth conductor.

55

Connect to s2 of the CT on the neutral to
earth link.
Also connect to the s2 of CTs connected
to L1, L2, L3.

2.5mm²

AWG 13

NOTE:- Terminals 56 to 59 are not fitted to the 7200 / 7300 series controller.