User manual - optima ups 6k/ 10k (english), Isotx, Circuit breakers selection – XMART Optima-RACK 10K User Manual

Page 14

Advertising
background image

USER MANUAL - OPTIMA UPS 6K/ 10K (ENGLISH)

______________________________________________________________________________________________________________________

20140805 Tower-Rack 6K-10K ISOTX

- 14

CIRCUIT

BREAKERS

SELECTION

Circuit breakers and cables must be selected to comply with below current ratings. Below table provide suggested values for
protection devices & cables according to standard conditions. User is responsible for revising and adequate cable selection
according to operation conditions and to comply with local regulations.

UPS

INPUT 220Vac 1Ph

OUTPUT 220Vac 1Ph

EXT. BATT (240Vdc)

MODEL

BREAKER & WIRING

BREAKER & WIRING

BREAKER & WIRING

6KVA

Output 220Vac

AC Breaker: 40A (Curve D)

Max. Nominal Current: 36A

Wiring (min. size):

10AWG (6 mm2)


AC Breaker: 40A (Curve D)

Max. Nominal Current: 36A

Wiring (min. size):

10AWG (6 mm2)


Breaker: 50A DC (Curve C)

Max. Nominal Current: 30A

DC

Wiring (min. size):

10 AWG (6 mm2)

10KVA

Output 220Vac

AC Breaker: 63A (Curve D)

Max. Nominal Current: 60A

Wiring (min. size):

8AWG (10 mm2)

AC Breaker: 63A (Curve D)

Max. Nominal Current: 60A

Wiring (min. size):

8AWG (10 mm2)

Breaker: 63A DC (Curve C)

Max. Nominal Current: 50A

DC

Wiring (min. size):

8 AWG (10 mm2)

ISOTX

UNIQUE OUTPUT: 1 x 120Vac

(100% Watts)

SEPARE OUTPUTS: 2 x 120Vac

(50% Watts C/U)

6KVA con ISOTX

Output 110/220V

Unique Output Capacity: 6000VA / 4800W

Output Voltage: 120Vac

AC Breaker: 80A (Curve D)

Max. Nominal Current: 70A

Wiring (min. size): 6AWG (16 mm2)

VA/W per Output: 3000VA / 2400W

Output Voltage: 120Vac

AC Breaker: 40A (Curve D)

Max. Nominal Current: 36A

Wiring (min. size): 10AWG (6 mm2)

10KVA con ISOTX

Output 110/220V

Unique Output Capacity: 10000VA / 8000W

Output Voltage: 120Vac

AC Breaker: 125A (Curve D)

Max. Nominal Current: 120A

Wiring (min. size): 3AWG (35 mm2)

VA/W per Output: 5000VA / 4000W

Output Voltage: 120Vac

AC Breaker: 63A (Curve D)

Max. Nominal Current: 60A

Wiring (min. size): 8AWG (10 mm2)

WIRE SUGGESTIONS ACCORDING TO "1999 NEC" BASED ON ROOM TEMPERATURE 30ºC & SINGLE COOPER CABLES WITHOUT
CONDUIT.

WARNING: The correct wire gauge or section is strongly affected by diverse factors such as: room temperature,
wire length, type of wire and kind of installation. User or his electrical contractor must assure an appropriate
selection for wire and other devices for complying with local electrical regulations and directives.

WARNING: For ISOTX models: When using two 110VAC outputs separately, each output only will be able to drive
50% of total UPS capacity. For example, for 10KVA UPS, each 110Vac output will drive 5KVA max.

Advertising
This manual is related to the following products: