USER MANUAL - OPTIMA UPS 6K/ 10K (ENGLISH)

______________________________________________________________________________________________________________________

20140805 Tower-Rack 6K-10K ISOTX

- 30

FUNCTION DISPLAY ACCORDING TO OPERATION MODE

Operation Mode

Description

LCD




ONLINE

* UPS ON
* Input AC source OK
* UPS output generated by inverter





ECO

* UPS in ON
* ECO mode activated.
* Input AC source is OK

* UPS output feed from AC input to save
energy.

* UPS in ON
* ECO mode activated.
* Input AC source out of acceptable range
* UPS output generated by inverter.


FREQUENCY CONVERTER
FUNCTION (CF)

CF function enable to generate output
frequency as selected.
IMPORTANT NOTE: When CF is activated
bypass mode is automatically disable and

maximum power output is de-rated to 60%
of standard maximum power output.



BATTERY MODE

When AC input source is out of range Ups
goes to battery mode to supply output from
taking energy from batteries.




BYPASS

If UPS is overloaded by big consuming load
connected at UPS output, UPS changes to
BYPASS mode feeding outlets from input AC
source. This mode can be set also by front
panel (by selecting “ON/MUTE” + “SELECT”
at same time).

FAULT STATUS

When UPS detects a failure, output will be

powered off and error code will be displayed
on LCD. (Example code 43).