13: BATTERY VOLTAGE ADJUSTMENT

LCD

Parameter 2: Select “Add” or “Sub” for adjusting battery voltage (Add or
Reduce)
Parameter 3: available adjustment value is from 0Vdc to 5.7Vdc. factory
set value is 0V.
*** WE STRONGLY RECOMMEND TO NOT CHANGE THIS FACTORY SET
VALUE **

14: BATTERY CHARGER ADJUSTMENT

LCD

Parameter 2: Select “Add” or “Sub” for adjusting battery charger voltage
(Add or Reduce)
Parameter 3: available adjustment value is from 0V a 9.9V. Factory set
value is 0Vdc
NOTE:
*Before changing this value batteries must be disconnected from UPS so

that charger output voltage can be measured without batteries interference.
*** WE STRONGLY RECOMMEND TO NOT CHANGE THIS FACTORY SET
VALUE **

15: OUTPUT VOLTAGE ADJUSTMENT

LCD

Parameter 2: Select “Add” or “Sub” for adjusting battery charger voltage
(Add or Reduce)
Parameter 3 available adjustment value is from 0V a 6.4V. Factory set
value is 0V.