Configuration menu functions and screens

01: Output Voltage Configuration

LCD

Parameter 3: Output Voltage Value
Output can be selected from following choices:
208: 208Vac (** Important Note)

220: 220Vac
230: 230Vac
240: 240Vac

** IMPORTANT NOTE: If output voltage is set to 208Vac, maximum power output is de-rated 10%. For example for a 10KVA UPS,
maximum power output will be 9KVA.

02: Output Frequency

LCD

60 Hz, CVCF mode

50 Hz, Normal mode

ATO

Parameter 2: Output Frequency
Output can be selected from following choices:

50.0Hz: 50.0Hz.
60.0Hz: 60.0Hz.
ATO: Automatic: Under this mode output frequency is selected according to input
frequency:
50Hz if input is (46Hz y 54Hz) and
60Hz if input is (56Hz y 64Hz).
ATO mode is factory default value.

Parameter 3: Frequency Mode
Adjusting parameter 3, can be selected CF Mode which is frequency converter mode
or NCF in NON converter mode.
CF: This mode allows fixing a fixed output frequency in parameter 2.
NCF: This mode allows output frequency was selected according to the input
meanwhile input frequency is inside allowed range. If input frequency is out of range
UPS will go to battery mode.

IMPORTANT NOTE ABOUT FREQUENCY CONVERSION FUNCTION "CF":

* When CF function is enable to generate an output with a different frequency value than input, bypass mode will be automatically
disable.
* When CF function is activated, maximum power output is de-rated to 60% of standard power output. For example: for 10KVA UPS
when CF is activated max. output power is 6KVA.