09: BATTERY BACKUP MAXIMUM TIME
LCD
Parameter 3: 
000~999: It sets maximum backup time from 0min to 999min. UPS will turn 
OFF to protect batteries when time is reached. 
DIS: IT disables this function and batteries will be used until reaching very low 
level. 
 
** WE STRONGLY RECOMMEND TO KEEP FACTORY SET VALUE 990 **
10: PROGRAMMABLE OUTPUTS
LCD
Parameter 3: It configures programmable outputs according to available 
options: 
 
ON: Programmable outputs are supplied without time restrictions. 
OFF: This option turns programmable outputs OFF. 
ATO: This option allows programmable outputs to turn off when timer value is 
reached (or very low voltage level, whatever occurs first). 
 
11: PROGRAMMABLE OUTPUTS CONFIGURATION
LCD
Parameter 2: 001. 
Menu for timer setting. 
 
Parameter 3: Shutdown time in minutes.  
Timer can be set from 0 to 300 min. 
Parameter 2: 002 
Menu for minimum battery voltage level setting. 
 
Parameter 3: Shutdown voltage in V.  
Minimum voltage can be set from 11.2Vdc - 13.6 Vdc. Programmable outlets 
are turned off when minimum voltage value is reached. 
12: HOT STAND BY: “NO-BATTERY STARTUP” FUNCTION
LCD
Ajuste
Parameter 2: HS.H 
Enable or disable Hot standby function. You may choose following two options 
in Parameter 3: 
YES: Hot standby function is enabled. It means the UPS is set to restart after AC 
recovery even without battery connected. 
NO: Hot standby function is disabled. The UPS is running at normal mode and 
can’t restart without battery