User manual - optima ups 6k/ 10k (english), General safety instructions – XMART Optima-RACK 10K User Manual

Page 4

Advertising
background image

USER MANUAL - OPTIMA UPS 6K/ 10K (ENGLISH)

______________________________________________________________________________________________________________________

20140805 Tower-Rack 6K-10K ISOTX

- 4

To enlarge batteries life expectancy it is recommendable to fully discharge

UPS one every 2 to 3 months

During UPS storage recharge batteries according to the following table:

1. GENERAL SAFETY INSTRUCTIONS

WARNING: It is required to read and understand this manual. Follow all instructions given in this manual for starting up and
operating this product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for
future consults.
WARNING: This product operates with dangerous voltages. It must be installed, operated and maintained ONLY by qualified
technicians trained for this kind of products. Service personnel MUST know and understand very well all electric risks related
to this product. UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or
negligent practices at the moment of install, starting up or maintain this product.
UPS manufacturer or distributor is not liable for any damage that might rise from misusing this unit or defective installation.
WARNING: If you are not qualified technician do not try to install, operate or repair this product.
WARNING
: Do not try to install, operate or repair this product if you are not accompanied by another qualified person able to
offer first aid support in case of emergency or accidents.
WARNING
: Internal area of this product is locked by screws. Do not try to access inside the UPS unless you are a qualified
technician. UPS must be checked, repaired and maintained by qualified personnel only.

CAUTION!!: ELECTRIC SHOCK RISK

CAUTION: There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power line.
CAUTION: Inside this equipment, due to internal batteries, there are ALWAYS dangerous voltages, thought the UPS is OFF and

unplugged of power line.

CAUTION: There are dangerous voltages in DC (Direct Current) Capacitors. Please Check Capacitor location in Figure 8.4.1.

Wait at least 10 minutes after turning off UPS before opening it to access inside.

DANGER: Power off UPS and unplugged it from AC Line before opening it to Access inside this unit.
CAUTION: Before starting the opening procedure, remove all jewelry and metallic objects such as: Rings, Watches, Bracelets,

etc., because they could contact conductive parts and components inside the UPS and this might cause discharges and/or
short circuits. Make sure using tools properly isolated to avoid electrical risks.


Transportation and Storage: Warnings and Recommendations

WARNING: This UPS must be transported only in its original package to be properly protected

WARNING: This equipment must be storage in dry and ventilated site, in upright position.

WARNING: Before storage this UPS, batteries must be recharged for 8 to 10 hours

WARNING: During long term storage UPS must be recharged periodically according to this manual.

WARNING: EQUIPMENT DISPOSAL


Out of service units:
It is strongly recommended to dispose this piece of equipment according to valid directives in your
country. At the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or
for some materials to be recycled.

Batteries: Do not throw it to fire (risk of explosion). Do not open the batteries, there are dangerous liquids inside

WARNING: BATTERIES MAINTENANCE

• Batteries capacity, in general (of all kinds), decrease with time and use.

• Our products contain high quality batteries only.

• Batteries useful life in our UPS is between 4 and 5 years, considering environment temperature under 25 ºC and

optimal operational conditions. This time can be dramatically reduced by high temperature and other adverse

operation condition.

• Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as

well as number and kind of equipments connected to UPS

• Batteries should be periodically tested to check capacity and assure and appropriate back up.




Storage Temperature

Recharging Frequency

Recharging Time

-25°C a +30°C

Every 4 months

During 6 hours

+30°C a +45°C

Every 2 months

During 6 hours

Advertising
This manual is related to the following products: