12.- ERROR CODES, ALARMS & TROUBLESHOOTING

ERROR / FAILURE CODES ON LCD

When a failure or alarm is detected by the UPS, an alarm or error code is presented in front panel LCD. This code or symbol
will allow to identify the problem. In case of failure or alarm, service center must revise the problem.

ERROR CODE ERROR DESCRIPTION

ICON

BEEP ALARM

1

Bus failure

Continous

Beep

2

Hi BUS Voltage

3

Low BUS Voltage

4

Bus Unbalanced

5

BUS shortcircuit

11

Inverter soft start failure

12

Inverter HI voltage

13

Inverter LOW voltage.

14

Inverter output short-circuit

SHORT

1A

Negative Voltage failure

21

Battery SCR Short-Circuit

24

Inverter Relay Short-Circuit

28

Battery connection problem

BATT. FAULT

35

Parallel Communication problem

36

UPS Output Short-Circuit

41

HIGH Temperature.

42

CPU communication problem

43

UPS Output Overload

OVER LOAD


ALARM

CODES

ON

LCD

ALARM DESCRIPTION

BEEP/Sec

LOW BATT.

Low Battery

1 beep / s

OVER LOAD

UPS Overload: High power consumption in Watts at
UPS output

2 beep / s

BATT. FAULT

Batteries disconnected

1 beep / s

EP

EPO (emergency power off) activated

1 beep / s

High Temperature

1 beep / s

Battery Charger Failure

1 beep / s

Input Fuse Activated

1 beep / s

Repetitive Overloads Detected (3 in 30 minutes)

1 beep / s

3F

Parallel Failure (**)

1 beep / s

FLASHING ICON

Battery Overload

1 beep / s

WARNING:

** Some alarms can block UPS avoiding normal operation of UPS until they are reset. Technician must

revise original error cause has been solved and then alarm must be reset by simultaneous selection of UP and DOWN
keys in front panel meanwhile UPS is in BYPASS mode (connected to AC source previous to select ON command).