Check Unit Safety Devices

SAFETY THERMOSTAT (Fig. 6)

The low water temperature cutout (LWTC) pro­

tects the unit against freeze-up due to operating mal­
function. The sensing bulb is inserted into a well
located in the leaving water nozzle. As installed, the
standard control is factory set to open at 36 ± 2 F,

breaking the control circuit and locking out unit.
The contacts remake at 5 ± 2 F above cutout point,
but the control circuit switch must be pressed to
OFF and then to ON for unit restart. This action re­
energizes the control circuit and starts the timer
under Time Guard® control.

The thermostat cuts out in a range down to -30 F,

but to obtain this range, the low-limit stop tab on the
underside of dial must be either cut or bent. Make
this adjustment only if necessary (when cooling
glycols or brines).

HIGH-PRESSURE SWITCH (HPS)

The HPS settings are nonadjuslable. Table 6

shows factory settings for this switch.

If HPS cuts out while unit is in normal operation

(2-1/2 minutes or more after compressor start-up),
compressor will stop and lock out. To restart com­

pressor, the ON-OFF control circuit switch must
be manually pressed to OFF and then to ON. The
timer will start, and after approximately 5-1/2 min­

utes, the compressor will start under Time Guard
control. If the pressure has not dropped to the HPS
cut-in point (see Table 6), the compressor will stop
again immediately and again lock out. Do not
attempt to restart until trouble is found and
corrected. Unless control circuit swdtch is pressed to
OFF at this time, timer will continue to run.

Table 6 — Pressure Switch Specifications

UNIT 30

HK

HL

PRESSURE
RANGE (psig)

High

Low

Fixed

10 to 90

Fixed

Adjustable

DIFFERENTIAL
SETTING (psi)

High

Low

96 ± 17 (Fixed) | 1 03 ± 19 (Fixed)

1 3 to 50 Adjustable

Cutout

Cut-in

Cutout

Cut-in

FACTORY
SETTING (psig)

High

Low

260 ± 10

29 ± 4 44 ± 4

335+10

29 ± 4 44 ± 4

LOW-PRESSURE SWEICH (EPS)

The EPS is bypas.sed for 2-1/2 minule.s after

compressor start on all start-ups. The EPS has an
adjustable range from 10 to 90 psig and a differential
of 13 to 50 psi. See Fig. 7. Table 6 shows factory

settings for this switch.

If EPS cuts out while unit is in normal operation

(any time after 2-1/2 minutes from compressor
start-up) timer starts and runs for approximately
5-1/2 minutes. The compressor then starts, by­
passing the EPS for 2-1/2 minutes under Time

Guard control. If the EPS cut-in pressure is reached

within 2-1/2 minutes, compressor continues to run;
if, on the other hand, the required pressure has not

built up, compressor stops at end of 2-1 /2 minutes

and locks out.

Do not attempt to restart unit until trouble has

been found and corrected. The LPS contacts must
be closed before compressor can be restarted after
lockout.

, RANGE ADJ SCREW

/ TURN CLOCKWISE TO RAISE

J

BOTH CUT-IN AND CUTOUT

7

^^G7PSI PER TURN)

/

aiWFFERENTIAL ADJ SCREW

TURN CLOCKWISE TO DECREASE

(8 PSI PER TURN). ONLY CUTOUT
CHANGES

(RIGHT SIDE OF CONTROL BOX, VIEWED FROM TOP)

Fig. 7 — Low-Pressure Switch (LPS)

Adjustment

Check Capacity Control System

DESCRIPTION

Capacity control is a system which loads and

unloads compressor cylinders and starts and stops
compressor to maintain load requirements. System
includes a 3-step temperature controller and cyl­
inder unloaders (see Table 2). Table 7 shows ca­
pacity control steps.

Table 7 — Capacity Control Steps

UNIT

30HK,

30HL

CONTROL

STEPS

%

CAP.

OPER

CYL

1

33

2

015

2

67

4

3

100

6

1

35

2*

020

2

50

2

3

100

4

025,
030

1
2

3

33
67

100

2
4

6

'Uses hot gas bypass.

3-STEP TEMPERATURE CONTROLLER

This controller consists of 3 load switches actu­

ated by pressures developed in a temperature­
sensing bulb located in return water line of chilled
water system. The controller is factory set to control
from return water temperature thru a cooling range
of 10 F. Sequence switches are factory calibrated
and sealed and should not require any field changes.

IMPOR 1 .\N 1. It a dilferent reiurn-waler cool­

ing range or leaving-water control is specified,
or if brine below 10 L' is to be used, controller
must be changed. Consult local Carrier repre­
sentative for proper control device.

10