Refer to Tables 4 and 5 for electrical data on indi­

vidual compressors and complete units. Compressor
usage is given in Tables 2 and 5.

ELECTRICAL BOX, CONTROL SECTION

Inside this section are relays, high- and low-

pressure cutouts, low water-temperature cutout,
timer, terminal strips and a 3-step temperature
controller. On the outside (control panel) are con­
trol circuit ON-OEF switch, partial load switch
(DLS), compressor run light, safety trip lights and
control circuit fuse. The control panel is hinged to

provide easy access to the controls inside.

^ Table 4 — Unit Voltage and Model Number*

VOLTS

UNIT 30HK.HL

015,020,025,030

208/230

5--

460

6--

575

1--

'Compiete number has 10 digits.

Example: 30HK020530.

UNBALANCED 3-PHASE SUPPLY VOLTAGE

Never operate a motor where a phase imbalance

in supply voltage is greater than 2%. Use the follow­
ing formula to determine the % voltage imbalance:
% Voltage Imbalance =

max voltage deviation from average voltage

* *

100 X-

average voltage

Example: Supply voltage is 240-3-60.

* ^

AB = 243 volts

BC = 236 volts
AC = 238 volts

Average Voltage

243 + 236 + 238

717

3

= 239 volts

Determine maximum deviation from average

voltage:

(AB) 243 - 239 = 4 volts
(BC) 239
(AC) 239

236
238

3 volts

1 volt

Maximum deviation is 4 volts.
Determine % voltage imbalance:

A

% Voltage Imbalance = 100 x

239

= 1.7%

This amount of phase imbalance is satisfactory

as it is below the maximum allowable 2%.

IMPOR 1 .-XN'l : li the ■'UppU \oliagc phase im­

balance is more than 2((', contact \our h>cal
electric uulits cornpain immcdiateU.

LQUIP GND

Control circuit power is from separate source, Incoming wires are

connected directly to terminals and on TB2.

EQUIPGMD — Equipment Ground

Fig. 3 — Wiring Schematic — Unit and

Control Power Supply

ELECTRICAL BOX, POWER SECTION

The main electrical power supply is brought in

thru the top of the electrical box, on the left-hand

side (see Fig. 1). The hole accommodates up to a
3-in. conduit. Pressure-lug connections on terminal
block are suitable for copper, copper-clad alumi­
num or aluminum wire, unless otherwise noted on a
label near the terminal block.

The power section contains: main power terminal

block, compressor circuit breaker with calibrated
magnetic trip (for compressor motor overload and
locked rotor protection), and compressor motor
contactors. The panel over this section is secured

with screws as a safety measure against casual entry
for purposes other than service.