Carrier 30HK User Manual

Page 14

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TROUBLESHOOTING GUIDE

SYMPTOMS

1

PROBABLE CAUSE

REMEDY

Compressor does not run !

Power line open

Reset circuit breaker.

!

Control circuit breaker tripped

Check control circuit for ground or
short.

s

Reset breaker.

j Safety tripped

Reset.

1

Tripped power breaker

Check the controls. Find cause of
trip and reset breaker.

Condenser circulating pump not

Power off — restart.

running

Pump binding — free pump.

1

j

Incorrect wiring — rewire.

Pump motor burned out — replace.

Loose terminal connection

Check connections.

Improperly wired controls

Check wiring and rewire.

1

Low line voltage

Check line voltage — determine
location of voltage drop and

remedy deficiency.

j

Compressor motor defective

Check motor winding for open or
short. Replace compressor, if

necessary.

;

i

Seized compressor

Replace compressor.

Compressor cycles on low-

i

Low-pressure control erratic in

Raise differential setting.

pressure control

action

Check capillary for pinches.

1

Replace control.

Compressor suction valve leaking

Replace valve plate.

Compressor suction shutoff valve
partially closed

Open valve.

Low refrigerant charge

Add refrigerant.

Plugged compressor suction

strainer

Clean strainer or replace.

Compressor loses oil

Leak in system

Repair leak.

Mechanical damage (blown piston

or broken discharge valve)

Repair damage or replace

compressor.

Oil trapped in line

Check piping for oil traps.

Crankcase heaters not energized
during shutdown

Check wiring and crankcase
heater relay. Replace heater if
necessary.

Frosted suction line

Expansion valve admitting excess
refrigerant

Adjust expansion valve. Replace
valve if defective.

Compressor cycles on high-

High-pressure control erratic in

Check capillary tube for pinches.

pressure control

action

Set control as required.

Compressor discharge valve
partially closed

Open valve, or replace if defective.

Air in system

Purge.

Condenser scaled

Clean condenser.

Condenser water pump or fans not
operating

Start pump — repair or replace if

defective.

Unit operates long or

Low refrigerant charge

Add refrigerant.

continuously

Control contacts fused

Replace control.

Air in system

Purge.

Partially plugged or plugged

expansion valve or strainer

Clean or replace.

Defective insulation

Replace or repair.

Service load too high

Keep doors and windows closed.

Inefficient compressor

Check valves, replace if necessary.

!4