6. Check leaving chilled water temperature to see

that it remains well above freezing.

7. Recheck compressor oil level. See Check Oil

Charge.

Check Refrigerant Feed Components

THERMOSTATIC EXPANSION VALVE (TXV)

This valve controls refrigerant flow. Valve is

activated by a temperature sensing bulb clamped to
suction line. The valve is factory set to maintain a
superheat of 8 F to 10 F. Do not change setting
unless absolutely necessary.

FILTER DRIER

The 30HK,HL015 thru 030 units (single com­

pressor) have sealed-type driers. When a drier must
be changed, the entire drier must be replaced. The
function of the filter drier is to maintain a clean,
dry system. The moisture indicator (below) can indi­
cate any need to change filter drier.

MOISTURE-LIQUID

INDICATOR

The indicator is located immediately ahead of

the TXV to provide a constant indication of refrig­
erant moisture content. It also provides a sight
glass for refrigerant liquid. Clear flow of liquid
refrigerant indicates sufficient charge in system.

Bubbles indicate under-charged system or presence
of noncondensables. Moisture in the system,
measured in parts per million (ppm), will change
color of indicator.

Unit must be in operation at least 12 hours

before moisture indicator will give an accurate
reading. With unit running, indicating element must
be in contact with liquid refrigerant to give true
moisture indication.

At first sign of moisture in the system, change

the filter drier. The tables below indicate when the
change is required.

30HK,HL01 5,020

COLOR

CONDITION

Green

Dry; moisture is below 45 ppm

Chartreuse

Caution: 45 ppm

Yellow

Wet; above 130 ppm

30HK,HL025,030

COLOR

CONDITION

Blue

Safe, dry

Light violet

First sign of moisture

Pink

Dangerous moisture level

LIQUID-LINE SERVICE VALVE

This valve provides a refrigerant charging port

and, in combination with the compressor discharge
service valve, allows the refrigerant to be pumped
into the high side.

LIQUID-LINE SOLENOID VALVE (HL only)

The solenoid valve closes when its circuit is in­

operative, either from capacity control or from any
safety trip.

PRESSURE RELIEF DEVICES

On HK units, a high-side pressure-relief valve is

factory installed on the condenser. The valve is set
to open at a maximum pressure of 385 psig (maxi­

mum design working pressure of the condenser).

For ЗОНЕ units, pressure relief device, designed

to relieve at 450 psig, is field supplied and installed
in the discharge line after the muffler according to

ANSI.B9.1 code requirements.

Additional pressure relief valves, properly se­

lected, must be field installed to protect field-
installed high-side equipment as may be required by
applicable codes.

A fusible plug is factory installed on the suction

line for low-side protection. This plug will relieve
on temperature rise to 170 F.

Most local codes require that a relief valve be

vented directly to outdoors. The vent line must not
he smaller than the relief valve outlet (518-in. SAE).

CHECK VALVE

A discharge-line check valve is supplied with each

condenseriess (HL) unit as standard equipment.
This valve should be located downstream from, but
close to, the hot gas muffler. The valve can be
mounted in either horizontal or vertical position.

The valve prevents migration of refrigerant from

condenser to compressor and cooler during off-
cycle of compressor.

Check Compressor Protection Devices

CIRCUIT BREAKER

The compressor is protected against an over­

current condition by a manual-reset calibrated-trip
circuit breaker.

IMPOR LAN I l'>o not bypass connections or
increase brcakci si/c ti> correct trouble. Deter­

mine the cause and correct before resetting
breaker.

MOTOR OVERTEMPERATURE

THERMOSTAT

On size 015 units, a sensor embedded in motor

windings protects against overtemperature.

On all other sizes, a sensor in the discharge side

of the compressor reacts to excessively high dis­
charge gas temperature and shuts off the com­
pressor. A high discharge gas temperature indicates
an overtemperature condition in motor windings.

CRANKCASE HEATER

The heater prevents absorption of liquid refrig­

erant by oil when compressor is not operating.

On size 015 units, the heater is secured by a clip;

on all other sizes, it is held in place by a bracket.

t. AU l ION; The hcatci must be light to prevent

il from backing out ot the crankcase. I he heater

will burn out if exposed to aii for an extended