The electric heater is wired into the 115-volt

control circuit thru normally closed contacts of
control relay in such a way that it is energized only
when compressor is not operating.

All heaters are 125 watts.

C .\L 1 ION: Never open an\ >witeh or discon­
nect that will de-encrgi/e crankcase healer un­

less unit IS being serviced or will be shut down
tor a prolonged period. .Alter such service or
prrdonged shutdown, energize crankcase heater
lor 24 hours before starting compressor.

TIME GUARD® CONTROL

This control protects compressor against short

cycling (Switch A on four-function timer).

FOUR-FUNCTION TIMER

Refer to Fig. 4 — Timer Cycle. The functions are

as follows:

Switch A (Contacts A-Al, A-A2) runs timer motor.
This provides a minimum of 5-1/2 minutes after
compressor stops before it can restart, to prevent
short cycling (Time Guard control).

Switch B (Contacts B-Bl, B-B2) provides 1-second
time delay for part-winding start and also provides
a lock-out function.
Switch D (Contacts D-D 1) provides a 2-1 / 2 minute
bypass of the low-pressure switch at start-up to
prevent nuisance trips under cold-start conditions.

Switch E (Contacts E-El) provides a 35-second by­
pass of the oil safety switch (OPS) at compressor
start-up (when OPS is used), if sufficient oil pressure
does not build up in this time, compressor stops.

0 OR 8 MiN.

POSITION DURING UNIT OPERATION-

COMPRESSOR STARTS

1 BBi

1 1

1--------------------------1

H 1—-1 SEC±05

H^SSECiZ

____ Щ_______ I . ............................................. 1

5

7 SEC±4 —И h

■«............^---------- 40SEC15

S DDI

NOTE: BLACK DENOTES CLOSED CONTACTS

Fig. 4 — Timer Cycle

OIL PRESSURE SAFETY SWITCH (OPS)

This control is standard on ЗОНЕ (condenserless)

units (020-030) and is available as an accessory for

30HK units (020-030). Refer to Fig. 5 for field
wiring connections. It is not available for the 015
unit.

The pressure switch is factory set at the following

pressures and should not be adjusted in the field.

SWITCH POSITION

PRESSURE SETTING

Close on rise

9 - 12 psi diff

Open on fall

4 - 6 psi diff

The oil pressure safety switch is wired in parallel

with Switch E of the 4-function timer. This arrange­
ment allows approximately 35 seconds for oil pres­
sure to reach normal operating level after com­
pressor starts. If the oil safety switch does not close
within 35 seconds, the compressor shuts down.

To restart the compressor, the control circuit

ON-OFF switch must be pressed to OFF and then to
ON. The timer will start and after approximately
5-1/2 minutes compressor will start. If normal oil
pressure is established within the next 35 seconds,
the compressor continues to run. If, however, the oil
pressure does not reach a safe level, the compressor
stops at the end of the 35 seconds and locks out.

(’.ли I ION; Di' not attempt to restart the com­

pressor tor a second time until the problem has
been determined and corrected.

REMOVE ORANGE Wl RE

OPS — Oil Pressure Safety Switch

TB — Terminal Board

Fig. 5 — Oil Pressure Safety Switch to

Control Box Wiring Connections

(020-030 Only)

LOW LIMIT STOP TAB

Fig. 6 — Safety Thermostat

(No. HH22CC050 Shown)