APPENDIX A — LOCAL DISPLAY TABLES (cont)

MODE — INPUTS (cont)

*The display text changes depending on the remote switch configuration (Configuration

UNIT

RM.CF). If RM.CF is set to 0 (No Remote

Switch), then the display text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or
“Unoccupied.” If RM.CF is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If RM.CF is set to 3 (Override Switch), then the display
text will be “No Override” or “Override.”

MODE — OUTPUTS

MODE — CONFIGURATION

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

4-20

4-20 MILLIAMP INPUTS

IAQ.M

IAQ Milliamps

ma

IAQ_MA

OAQ.M

OAQ Milliamps

ma

OAQ_MA

SP.R.M

SP Reset milliamps

ma

SPRST_MA

DML.M

4-20 ma Demand Signal

ma

DMDLMTMA

forcible

EDR.M

EDT Reset Milliamps

ma

EDTRESMA

ORH.M

OARH Milliamps

ma

OARH_MA

RRH.M

RARH Milliamps

ma

RARH_MA

BP.M

BP Milliamps

ma

BP_MA

BP.M.T

Bldg. Pressure Trim (ma)

–2.0 - 2.0

BPMATRIM

config

SP.M

SP Milliamps

ma

SP_MA

SP.M.T

Static Press. Trim (ma)

–2.0 - 2.0

SPMATRIM

config

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

FANS

FANS

S.FAN

Supply Fan Relay

ON/OFF

SFAN_RLY

S.VFD

Supply Fan VFD Speed

0-100

%

SFAN_VFD

P.E.A

Power Exhaust Relay A

ON/OFF

PE_A

P.E.B

Power Exhaust Relay B

ON/OFF

PE_B

P.E.C

Power Exhaust Relay C

ON/OFF

PE_C

CD.F.A

Condenser Fan Circuit A

ON/OFF

CONDFANA

CD.F.B

Condenser Fan Circuit B

ON/OFF

CONDFANB

COOL

COOLING

A1

Compressor A1 Relay

ON/OFF

CMPA1

A2

Compressor A2 Relay

ON/OFF

CMPA2

MLV

Min. Load Valve (HGBP)

ON/OFF

MLV

B1

Compressor B1 Relay

ON/OFF

CMPB1

B2

Compressor B2 Relay

ON/OFF

CMPB2

HEAT

HEATING

HT.1

Heat Relay 1

ON/OFF

HS1

HT.2

Heat Relay 2

ON/OFF

HS2

HT.3

Relay 3 W1 Gas Valve 2

ON/OFF

HS3

HT.4

Relay 4 W2 Gas Valve 2

ON/OFF

HS4

HT.5

Relay 5 W1 Gas Valve 3

ON/OFF

HS5

HT.6

Relay 6 W2 Gas Valve 3

ON/OFF

HS6

H.I.R

Heat Interlock Relay

ON/OFF

HIR

forcible

ECON

ECONOMIZER

ECN.P

Economizer Act.Curr.Pos.

0-100

%

ECONOPOS

ECN.C

Economizer Act.Cmd.Pos.

0-100

%

ECONOCMD

forcible

E.PWR

Economizer Power Relay

ON/OFF

ECON_PWR

forcible

GEN.O

GENERAL OUTPUTS

ALRM

Remote Alarm/Aux Relay

ON/OFF

ALRM

forcible

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

PAGE NO.

UNIT

UNIT CONFIGURATION

C.TYP

Machine Control Type

1 - 6 (multi-text strings)

CTRLTYPE

4

27,28,32,35-37,
63,75,96

CV.FN

Fan Mode (0=Auto, 1=Cont)

0 - 1 (multi-text strings)

FAN_MODE

1

27,28,35,36

RM.CF

Remote Switch Config

0 - 3 (multi-text strings)

RMTINCFG

0

31,35,36,74

CEM

CEM Module Installed

Yes/No

CEM_BRD

No

35,36

TCS.C

Temp.Cmp.Strt.Cool Factr

0 - 60

min

TCSTCOOL

0

35,36

TCS.H

Temp.Cmp.Strt.Heat Factr

0 - 60

min

TCSTHEAT

0

36

SFS.S

Fan Fail Shuts Down Unit

Yes/No

SFS_SHUT

No

36,60,100

SFS.M

Fan Stat Monitoring Type

0 - 2 (multi-text strings)

SFS_MON

0

35,36,60,100

VAV.S

VAV Unocc.Fan Retry Time

0 - 720

min

SAMPMINS

50

36

SIZE

Unit Size (20-60)

20 - 60

UNITSIZE

20

36,38,42,49

DP.XR

Disch.Press. Transducers

Yes/No

DP_TRANS

No

36,97

SP.XR

Suct. Pres. Trans. Type

0 - 1 (multi-text strings)

SPXRTYPE

0

36

RFG.T

Refrig: 0=R22 1=R410A

0 - 1 (multi-text strings)

REFRIG_T

1

36,38,49

CND.T

Cnd HX Typ:0=RTPF 1=MCHX

0 - 1 (multi-text strings)

COILTYPE

0

36,38,49

MAT.S

MAT Calc Config

0 - 2 (multi-text strings)

MAT_SEL

1

36,47,48

MAT.R

Reset MAT Table Entries?

Yes/No

MATRESET

No

36,47,48

MAT.D

MAT Outside Air Default

0-100

%

MATOADOS

20

36,37

ALTI

Altitude……..in feet:

0 - 60000

ALTITUDE

0

36,37

DLAY

Startup Delay Time

0 - 900

sec

DELAY

0

36,37

STAT

TSTAT-Both Heat and Cool

Yes/No

TSTATALL

No

36,37

AUX.R

Auxiliary Relay Config

0 - 3

AUXRELAY

0

36,37

SENS

INPUT SENSOR CONFIG

36

SENS

SPT.S

Space Temp Sensor

Enable/Disable

SPTSENS

Disable

27,28,36,37

SENS

SP.O.S

Space Temp Offset Sensor

Enable/Disable

SPTOSENS

Disable

36,37,75

SENS

SP.O.R

Space Temp Offset Range

1 - 10

SPTO_RNG

5

36,37,75

SENS

RRH.S

Return Air RH Sensor

Enable/Disable

RARHSENS

Disable

36,37,61,97,99

SENS

FLT.S

Filter Stat.Sw.Enabled ?

Enable/Disable

FLTS_ENA

Disable

36,37,60,100