Hot gas bypass, Space temperature offset, Time clock configuration – Carrier WEATHERMAKER 48/50AJ User Manual

Page 75: Hour and minute ( hh.mm ), Month of year ( mnth ), Day of month ( dom ), Day of week ( day ), Year ( year ), Local time schedule ( sch.l )

Advertising
background image

75

Table 89 — Switch Logic Configuration

Table 90 — Display Configuration

Table 91 — Remote Switch Configuration

Remote Switch Logic Configuration (Configuration

SW.LG

RMI.L) — The control allows for the configuration

of a normally open/closed status of the remote input switch via

RMI.L. If this variable is configured OPEN, then when the

switch is open, the remote input switch perceives the logic state

as OFF. Correspondingly, if RMI.L is set to CLOSED, the re-

mote input switch will perceive a closed switch as meaning

OFF. See Table 92.

Hot Gas Bypass —

Hot gas bypass is an active part of

the A-Series ComfortLink™ capacity staging and minimum

evaporator load protection functions. It is controlled though the

Minimum Load Valve function.

The hot gas bypass option consists of a solenoid valve with

a fixed orifice sized to provide a nominal 3-ton evaporator load

bypass. A hot gas refrigerant line routes the bypassed hot gas

from Circuit A’s discharge line to Circuit A’s evaporator

distributor. When the unit control calls for hot gas bypass, the

hot gas enters the evaporator coil and adds refrigeration load

to the compressor circuit to reduce the cooling effect from

Circuit A.

The hot gas bypass system is a factory-installed option

installed on Circuit A only. This function is enabled at Config-

uration

COOL

MLV. When this function is enabled, an

additional stage of cooling capacity is provided by the unit

control staging sequences (see Tables 52, 54, 58, and 60).

Space Temperature Offset —

Space temperature off-

set corresponds to a slider on a T56 sensor that allows the occu-

pant to adjust the space temperature by a configured range

during an occupied period. This sensor is only applicable to

units that are configured as either 2-Stage SPT or Multi-Stage

SPT control (Configuration

UNIT

C.TYP = 5 or 6).

Space Temperature Offset Sensor (Configuration

UNIT

SENS

SP.O.S) — This configuration disables the reading

of the offset slider.
Space Temperature Offset Range (Configuration

UNIT

SENS

SP.O.R) — This configuration establishes

the range, in degrees F, that the T56 slider can affect SPTO

when adjusting the slider from the far left (-SP.O.R) to the far

right (+SP.O.R). The default is 5° F.
Space Temperature Offset Value (Temperatures

AIR.T

SPTO) — The Space Temperature Offset Value is the read-

ing of the slider potentiometer in the T56 that is resolved to

delta degrees based on SP.O.R.

TIME CLOCK CONFIGURATION

This section describes each Time Clock menu item. Not

every point will need to be configured for every unit. Refer to

the Controls Quick Start section for more information on what

set points need to be configured for different applications. The

Time Clock menu items are discussed in the same order that

they are displayed in the Time Clock table. The Time Clock

table is shown in Table 93.

Hour and Minute (HH.MM) —

The hour and minute

of the time clock are displayed in 24-hour, military time. Time

can be adjusted manually by the user.

When connected to the CCN, the unit can be configured to

transmit time over the network or receive time from a network

device. All devices on the CCN should use the same time. Only

one device on the CCN should broadcast time or problems will

occur.

Month of Year (MNTH) —

This variable is the current

month of the calendar year.

Day of Month (DOM) —

This variable is the current

day (1 to 31) of the month.

Day of Week (DAY) —

This variable is the current day

of the week (Monday = 1 through Sunday = 7).

Year (YEAR) —

This variable is the current year (for ex-

ample, 2005).

Local Time Schedule (SCH.L) —

This submenu is

used to program the time schedules. There are 8 periods

(PER.1 through PER.8). Each time period can be used to set

up a local schedule for the unit.

ITEM

EXPANSION

RANGE

CCN POINT

DEFAULT

SW.LG

SWITCH LOGIC: NO / NC

FTS.L

Filter Status Inpt-Clean

Open/Close

FLTSLOGC

Open

IGC.L

IGC Feedback - Off

Open/Close

GASFANLG

Open

RMI.L

RemSw Off-Unoc-Strt-NoOv

Open/Close

RMTINLOG

Open

ECS.L

Economizer Switch - No

Open/Close

ECOSWLOG

Open

SFS.L

Fan Status Sw. - Off

Open/Close

SFSLOGIC

Open

DL1.L

Dmd.Lmt.Sw.1 - Off

Open/Close

DMD_SW1L

Open

DL2.L

Dmd.Lmt.2 Dehumid - Off

Open/Close

DMD_SW2L

Open

IAQ.L

IAQ Disc.Input - Low

Open/Close

IAQINLOG

Open

FSD.L

Fire Shutdown - Off

Open/Close

FSDLOGIC

Open

PRS.L

Pressurization Sw. - Off

Open/Close

PRESLOGC

Open

EVC.L

Evacuation Sw. - Off

Open/Close

EVACLOGC

Open

PRG.L

Smoke Purge Sw. - Off

Open/Close

PURGLOGC

Open

ITEM

EXPANSION

RANGE

UNITS

POINT

DEFAULT

TEST

Test Display LEDs

ON/OFF

TEST

Off

METR

Metric Display

ON/OFF

DISPUNIT

Off

LANG

Language Selection

0-1(multi-text strings)

LANGUAGE

0

PAS.E

Password Enable

ENABLE/DISABLE

PASS_EBL

Enable

PASS

Service Password

0000-9999

PASSWORD

1111

ITEM

EXPANSION

RANGE

CCN

POINT

REMT

Remote Input State

ON/OFF

RMTIN

RM.CF

Remote Switch Config 0 - 3

RMTINCFG

RMI.L

RemSw
Off-Unoc-Strt-NoOv

Open/Close

RMTINLOG

ITEM

EXPANSION

RANGE

UNITS

CCN

POINT

SP.O.S

Space Temp
Offset Sensor

Enable/
Disable

SPTOSENS

SP.O.R

Space Temp
Offset Range

1 - 10

SPTO_RNG

SPTO

Space Temperature
Offset

+- SP.O.R ^F

SPTO